| 2009-11-04 10:43:42 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PLAN HAS TWO EXHAUST FAN SCHEDULES. ONE FOR A |
| | "NUTONE" 50 CFM FAN AND ONE FOR A "GREENHECK" 70 CFM |
| | FAN. THERE IS ONLY ONE EF-1 SHOWN ON THE PLANS. PLEASE |
| | COORDINATE FLOOR PLAN AND EQUIPMENT SCHEDULES IN |
| | ACCORDANCE WITH FBC-M 304.1 AND 304.11. SEE ALSO NEXT |
| | COMMENT REGARDIN REQUIRED EXHAUST RATES. |
| | |
| | 2. PLAN SHOWS EITHER 50 OR 70 CFM OF EXHAUST FOR THE |
| | BEAUTY SALON. PER ASHRAE 62.1-2004 TABLE 6-4, THE |
| | REQUIRED EXHAUST RATE FOR THIS SPACE IS 0.12 CFM/SQ. |
| | FT. FOR A TOTAL OF 205 CFM. PROVIDE THE MINIMUM EXHAUST |
| | RATE AS REQUIRED PER THIS SECTION. |
| | |
| | 3. THE VENTILATION RATE DOES NOT MEET THE MINIMUM |
| | VENTILATION RATE AS REQUIRED PER ASHRAE 62.1-2004 TABLE |
| | 6-1. THE MINIMUM VENTILATION RATE FOR A HAIR AND NAIL |
| | SALON OF 342 SQ.FT. WOULD BE APPROX 220 CFM. SHOW HOW |
| | 220 CFM OF OUTDOOR AIR IS TO BE PROVIDED TO THIS SPACE |
| | IN ACCORDANCE WITH THIS SECTION AND FBC-M 403.4. |
| | |
| | 4. HAIR SALON IS GIVEN AN AIR CLASSIFICATION OF 2. WHAT |
| | IS THE AIR CLASSIFICATION OF THE SURROUNDING SPACES? |
| | DECLARE THIS CLASSIFICATION ON PLANS WITH JUSTIFICATION |
| | IN ACCORDANCE WITH ASHRAE 62.1-2004 SECTION 5.17.4. AT |
| | THIS TIME IT IS NOT CLEAR WHETHER AIR CAN BE |
| | RECIRCULATED FROM THE HAIR SALON TO ADJACENT SPACES VIA |
| | RETURN AIR. |
| | |