| 2009-10-27 15:57:03 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005 |
| | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING |
| | |
| | 1} 401.4 FBC EXISTING BUILDING CODE. THE DESIGN |
| | PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF |
| | ALTERATION PURSUANT TO SECTIONS 403, 404 AND 405 OF THE |
| | EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE |
| | PLAN. |
| | |
| | 2} 302.1 GENERAL. STRUCTURES OR PORTIONS OF STRUCTURES |
| | SHALL BE CLASSIFIED WITH RESPECT TO OCCUPANCY------, |
| | INDICATE SAME ON THE PLAN, ALSO INDICATE IF THIS IS A |
| | CHANGE OF OCCUPANCY PER CHAPTER 9 EXISTING BUILDING |
| | CODE FBC 2007. |
| | |
| | 3} PANEL"A" IS LOCATED IN A STORAGE CLOSET WHICH MAY BE |
| | IN VIOLATION OF 110.26 FOR CLEARANCES IT STORED ITEMS |
| | ARE IN THE REQUIRED FREE SPACE, AND 240.24 (D) NOT IN |
| | VICINITY OF EASILY IGNITIBLE MATERIAL OVERCURRENT |
| | DEVICES SHALL NOT BE LOCATED IN THE VICINITY OF EASILY |
| | IGNITIBLE MATERIAL, SUCH AS IN CLOTHES CLOSETS, AND |
| | WOUD ALSO BE A VIOLATION IF CHEMICALS ARE STORED IN |
| | THIS SPACE. A SAFER LOCATION WOUD BE ON THE WALL |
| | OUTSIDE AND ADJACENT TO THE CLOSET |
| | |
| | 4} FBC 13-415.AB.1.2 SPACE CONTROL. EACH SPACE ENCLOSED |
| | BY CEILING-HEIGHT PARTITIONS SHALL HAVE AT LEAST ONE |
| | CONTROL DEVICE TO INDEPENDENTLY CONTROL THE GENERAL |
| | LIGHTING WITHIN THE SPACE. EACH MANUAL DEVICE SHALL BE |
| | READILY ACCESSIBLE AND LOCATED SO THE OCCUPANTS CAN SEE |
| | THE CONTROLLED LIGHTING |
| | |
| | 5} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE |
| | INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A |
| | SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING |
| | SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD |
| | DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR |
| | LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING |
| | FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN |
| | USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING |
| | POWER IDENTIFIED IN ACCORDANCE WITH SECTION |
| | 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING |
| | POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH |
| | SECTION13-415.B.1 THIS CAN BE DEMONSTRATED ON THE PLANS |
| | INDICATING THE WATTAGES OF THE LUMINAIRES CHOSEN FOR |
| | THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS. |
| | INDICATE WATTAGES ON THE FIXTURE SCHEDULE TO CORRELATE |
| | WITH THE ONES IN THE CALCULATIONS. |
| | |
| | 6} THE ADDRESS IN THE TITLE BLOCK, SHEET E-1IS |
| | INCORRECT. PLEASE INCLUDE THE ADDRESS AND SUITE/UNIT |
| | NUMBER OF THE PROJECT ON THE PLANS PER 106.1.1 FBC AS |
| | AMENDED. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |