2009-11-02 14:40:45RESIDENTIAL ELECTRICAL PLAN REVIEW
 PERMIT: 09100416/ 09100417
 ADD: 2420 MEDINA WAY
 CONT: D&A BUILDERS/ ELECTRICAL EXPRESS
 TEL: (561)662-6226
  
 1A) PLANS SUBMITTED AFTER OCT. 1/ 2009 SHALL BE
 DESIGNED TO THE 2008 NEC.
  
 1B) PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDER THIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
 FOR THIS REVIEW A LEVEL 2 ALTERATION WAS CONSIDERED
 EITHER DELETING OR EXTENDING SYTEMS.
  
 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING KITCHEN
 COUNTERSPACE AS GFI/GFI PROTECTED AS REQUIRED PER
 210.8A-6 PLANS DO NOT INDICATE COMPLIANCE IF EXISTING
 INDICATE AS SUCH..
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS. ON EACH LEVEL OF A
 MULTI-LEVEL DWELLING UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING TO FLOORS ABOVE
 AND IN THE VICINITY OF BEDROOMS. PLEASE ALSO NOTE, SD'S
 ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND KITCHENS. ABOVE
 PER:FBC 905.2, NFPA-72 8-1.4
  
 4) ARC FAULT PROTECTION PROTECTION IS NOW REQUIRED IN
 RESIDENTIAL OCCUPANCIES ON ALL 15 AND 20 AMP BRANCH
 CIRCUITS THAT ARE NOT ALREADY REQUIRED TO BE PROTECTED
 BY GROUND FAULT INTERRUPTERS CIRCUITS (GFCI) OR OVER
 120 VOLTS 2110.12(B)
  
 5) MULTI-WIRE BRANCH CIRCUITS THAT SHARE A COMMON
 GROUND CONDUCTOR (NEUTRAL) MUST SHARE A COMMON
 DISCONNECT OR THE NEUTRALS MUST BE DISCONNECTED AT THE
 SAME TIME 210.4(B).
  
 6) 2008 NEC-NEW OCCUPIABLE BALCONIES AND PORCHES OVER
 20 SQ FT MUST NOW HAVE A RECEPTACLE OUTLET (GFCI
 PROTECTED) (210.52(E)(3).
  
 7) IN NEITHER THE BATHROOMS OR HALF BATHS DO THE PLANS
 INDICATE GFIC OUTLETS. BATHROOM GFIC OUTLET PLANS FAIL
 TO INDICATE COMPLIANCE WITH SECTION 210.11 (C)(3)
 BATHROOM BRANCH CIRCUITS IN ADDITION TO THE NUMBER OF
 BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS
 SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S).
  
 8) PLEASE REVIEW THE MASTER BEDROOM CLOSET CEILING
 FIXTURE LOCATION AS WELL AS THE GUEST ROOM# 1 CLOSET
 CEILINF FIXTURE. SEE 410.16(C) (1-5) & 410.16.2
 DEFINITION.
  
 9) NOTE: PLEASE SEE MISSING RECEPTS FOR FRONT AND/OR
 REAR OF DWELLING. 210.52E/ EXISTING BUILDING CODE
 708.3.5 MINIMUM LIGHTING OUTLETS. AT LEAST ONE LIGHTING
 OUTLET SHALL BE PROVIDED WITH ELECTRIC POWER, TO
 ILLUMINATE OUTDOOR ENTRANCES AND EXITS.
  
 10) NOTE: PLEASE SEE MISSING RECEPT REQ'D FOR A/C
 EQUIPMENT. 210.63
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved