| 2009-11-02 14:40:45 | RESIDENTIAL ELECTRICAL PLAN REVIEW |
| | PERMIT: 09100416/ 09100417 |
| | ADD: 2420 MEDINA WAY |
| | CONT: D&A BUILDERS/ ELECTRICAL EXPRESS |
| | TEL: (561)662-6226 |
| | |
| | 1A) PLANS SUBMITTED AFTER OCT. 1/ 2009 SHALL BE |
| | DESIGNED TO THE 2008 NEC. |
| | |
| | 1B) PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING |
| | BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO |
| | WHAT LEVEL ALTERATION WILL BE COMPLETED UNDER THIS |
| | PERMIT. |
| | 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 403, 404 AND 405 OF THIS CODE. |
| | FOR THIS REVIEW A LEVEL 2 ALTERATION WAS CONSIDERED |
| | EITHER DELETING OR EXTENDING SYTEMS. |
| | |
| | 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING KITCHEN |
| | COUNTERSPACE AS GFI/GFI PROTECTED AS REQUIRED PER |
| | 210.8A-6 PLANS DO NOT INDICATE COMPLIANCE IF EXISTING |
| | INDICATE AS SUCH.. |
| | |
| | 3) NOTE: SMOKE DETECTORS ARE REQUIRED INSIDE AND |
| | OUTSIDE ALL SLEEPING ROOMS. ON EACH LEVEL OF A |
| | MULTI-LEVEL DWELLING UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING TO FLOORS ABOVE |
| | AND IN THE VICINITY OF BEDROOMS. PLEASE ALSO NOTE, SD'S |
| | ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND KITCHENS. ABOVE |
| | PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | 4) ARC FAULT PROTECTION PROTECTION IS NOW REQUIRED IN |
| | RESIDENTIAL OCCUPANCIES ON ALL 15 AND 20 AMP BRANCH |
| | CIRCUITS THAT ARE NOT ALREADY REQUIRED TO BE PROTECTED |
| | BY GROUND FAULT INTERRUPTERS CIRCUITS (GFCI) OR OVER |
| | 120 VOLTS 2110.12(B) |
| | |
| | 5) MULTI-WIRE BRANCH CIRCUITS THAT SHARE A COMMON |
| | GROUND CONDUCTOR (NEUTRAL) MUST SHARE A COMMON |
| | DISCONNECT OR THE NEUTRALS MUST BE DISCONNECTED AT THE |
| | SAME TIME 210.4(B). |
| | |
| | 6) 2008 NEC-NEW OCCUPIABLE BALCONIES AND PORCHES OVER |
| | 20 SQ FT MUST NOW HAVE A RECEPTACLE OUTLET (GFCI |
| | PROTECTED) (210.52(E)(3). |
| | |
| | 7) IN NEITHER THE BATHROOMS OR HALF BATHS DO THE PLANS |
| | INDICATE GFIC OUTLETS. BATHROOM GFIC OUTLET PLANS FAIL |
| | TO INDICATE COMPLIANCE WITH SECTION 210.11 (C)(3) |
| | BATHROOM BRANCH CIRCUITS IN ADDITION TO THE NUMBER OF |
| | BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS |
| | SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE |
| | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). |
| | |
| | 8) PLEASE REVIEW THE MASTER BEDROOM CLOSET CEILING |
| | FIXTURE LOCATION AS WELL AS THE GUEST ROOM# 1 CLOSET |
| | CEILINF FIXTURE. SEE 410.16(C) (1-5) & 410.16.2 |
| | DEFINITION. |
| | |
| | 9) NOTE: PLEASE SEE MISSING RECEPTS FOR FRONT AND/OR |
| | REAR OF DWELLING. 210.52E/ EXISTING BUILDING CODE |
| | 708.3.5 MINIMUM LIGHTING OUTLETS. AT LEAST ONE LIGHTING |
| | OUTLET SHALL BE PROVIDED WITH ELECTRIC POWER, TO |
| | ILLUMINATE OUTDOOR ENTRANCES AND EXITS. |
| | |
| | 10) NOTE: PLEASE SEE MISSING RECEPT REQ'D FOR A/C |
| | EQUIPMENT. 210.63 |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |