Plan Review Notes
Plan Review Notes For Permit 09100379
Permit Number 09100379
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-11-17 14:41:07*****DENIED*****
  
  
 1. THE ACTUAL/CORRECT ADDRESS FOR THE PROJECT SITE
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 2. ONLY ONE OF THE THREE SUBMITTED PLAN SETS IS SIGNED
 AND SEALED BY THE PROFESSIONAL ENGINEER. THE OTHER TWO
 ARE COPIES.
  
 3. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 4. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 5. SPECIFY THE OCCUPANCY TYPE AND OCCUPANT LOAD FOR THE
 PROPOSED PROJECT SITE.
  
 6. BASED UPON THE OCCUPANCY TYPE AND OCCUPANT LOAD
 ASKED FOR ABOVE, THERE MAY BE A POOSSIBILITY THAT THIS
 SPACE MAY BE REQUIRED TO HAVE FIRE SPRINKLERS.
  
 7. SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 8. INCLUDE TRAVEL DISTANCES TO EXITS SHOWN ON THE LIFE
 SAFETY PLAN.
  
 9. ADDITIONAL EXIT LIGHT SIGNS MAY BE REQUIRED. VERIFY
 THAT THE EXIT SIGNS ARE PLACED SUCH THAT NO POINT IN AN
 EXIT CORRIDOR IS IN THE RATED VIEWING DISTANCE OR 100
 FEET, WHICHEVER IS LESS, FROM THE NEAREST SIGN.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722