| Plan Review Notes For Permit 09100379 |
| Permit Number |
09100379 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-11-17 14:41:07 | *****DENIED***** | | | | | | | | | 1. THE ACTUAL/CORRECT ADDRESS FOR THE PROJECT SITE | | | SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN | | | SHEET. | | | | | | 2. ONLY ONE OF THE THREE SUBMITTED PLAN SETS IS SIGNED | | | AND SEALED BY THE PROFESSIONAL ENGINEER. THE OTHER TWO | | | ARE COPIES. | | | | | | 3. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 4. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE | | | REFERENCED. | | | | | | 5. SPECIFY THE OCCUPANCY TYPE AND OCCUPANT LOAD FOR THE | | | PROPOSED PROJECT SITE. | | | | | | 6. BASED UPON THE OCCUPANCY TYPE AND OCCUPANT LOAD | | | ASKED FOR ABOVE, THERE MAY BE A POOSSIBILITY THAT THIS | | | SPACE MAY BE REQUIRED TO HAVE FIRE SPRINKLERS. | | | | | | 7. SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH | | | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 8. INCLUDE TRAVEL DISTANCES TO EXITS SHOWN ON THE LIFE | | | SAFETY PLAN. | | | | | | 9. ADDITIONAL EXIT LIGHT SIGNS MAY BE REQUIRED. VERIFY | | | THAT THE EXIT SIGNS ARE PLACED SUCH THAT NO POINT IN AN | | | EXIT CORRIDOR IS IN THE RATED VIEWING DISTANCE OR 100 | | | FEET, WHICHEVER IS LESS, FROM THE NEAREST SIGN. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|