| 2009-11-04 10:36:18 | BUILDING PLAN REVIEW |
| | PERMIT: 09100379 |
| | ADD: 500 BELVEDERE SUITE 642 |
| | CONT: QUAOM CONSTRUCTION |
| | TEL: (561)722-2303 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLEASE SEE THE COUNTY PROPERTY APPRAISERS WEBSITE |
| | FOR THE SITE ADDRESS OF 500 BELVEDERE PLEASE ALSO |
| | PROVIDE THTE SUITE OR TENANT UNIT NUMBER(642) ON BOTH |
| | THE PERMIT APPLICATION AND PLANS IN BOTH CASES THE |
| | WRONG ADDRESS INFORMATION IS PROVIDED. |
| | |
| | 2) THE SUBMITTED PLANS FROM P E LUIS LOPEZ ONLY ONE |
| | SEET IS ORIGINAL SIGNATURE AND SEAL THE OTHERS ARE |
| | COPIES OF SIGNED AND SEALED PLANS.61G15-23.002(2) FL. |
| | ADMIN. CODE. PLANS SIGNED & SEALED BY A PROFESSIONAL |
| | ENGINEER SHALL INCLUDE EITHER THE: NAME, ADDRESS AND |
| | LICENSE NUMBER OF THE ENGINEER OR, THE NAME AND LICENSE |
| | NUMBER OF THE ENGINEER AND THE NAME, ADDRESS AND |
| | CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS THROUGH WHICH THE ENGINEER IS PRACTICING |
| | (471.025 F.S. AND 471.023 F.S.). |
| | |
| | 3) SHEET A-2 INDICATES THIS TO BE A MERCANTILE |
| | OCCUPANCY, PLEASE PROVIDE A LIFE SAFETY PLAN WITH TABLE |
| | & SEATING. WHEN USING TABLE 1004.1.1 WITH 15 FT NET FOR |
| | THE SEATING AREA, BAR USING THE ACTUAL 13 SEATS AT THE |
| | BAR, 2 EMPLOYEES IN KITCHEN, 1 AT THE BAR AND 17 IN THE |
| | VACINITY OF THE POOL TABLES THE OCCUPANT LOAD IS 88 |
| | OCCUPANTS, THIS PUTS YOU OVER THE MERCANTILE OCCUPANCY |
| | AND INTO A A2 RESTARAUNT, BAR AND LOUGE CATEGORY. SEE |
| | SECTION 303.1 AND 309.1 FOR MERCANTILE. |
| | PLEASE UPDATE PLANS.THIS TRIGGERS IN THE EXISTING |
| | BUILDING CODE, CHAPTER 9 CHANGE OF OCCUPANCY FOR THE |
| | REVIEW. PLEASE UPDATE PLANS AND INDICATE THE EGRESS |
| | PATH FOR EXITING THE TENANT SPACE. |
| | |
| | 4) 2007 EXISTING BUILDING CODE 2007/ W 2009 SUPPLEMENTS |
| | SECTION 912.1.1.2 CHANGE OF OCCUPANCY CLASSIFICATION |
| | WITH SEPERATION . PLEASE REVIEW THE OCCUPANCY |
| | CLASSIFICATION IS TO BE BROUGHT UP TO THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE SEE 508.3.3 REQUIRING A 2 |
| | HR OCCUPANCY SEPERATION BETWEEN THTE NEW A2 OCCUPANCY |
| | AND THE MERCANTILE TENANT TO THE EAST. |
| | |
| | 5) PLEASE PROVIDE INTERIOR FINISH INFORMATION EXT BLD |
| | CODE 912.1.2 THE PLANS CURRENTLY INDICATE THIS BUILDING |
| | IS A NON-SPRINKLERED BUILDING SEE FL BLD CODE 803.1 & |
| | TABLE 803.5. UPDATE PLANS. |
| | |
| | 6) PLEASE REVIEW EXT BLD CODE 912.2.1 FIRE SPRINKLER |
| | SYSTEMS AND REQUIREMENTS, A NEW OCCUPANCY, CHANGE OF |
| | OCCUPANCY TRIGGERS THIS REQUIREMENT UNDER THE FLORIDA |
| | BUILDING CODE CHAPTER 9, REVIEW903.2.1.2(2) & (4). FOR |
| | RESTAURANT AND NIGHTCLUBS OR SIMILAR USAGE WHEN THE |
| | OCCUPANT LOAD IS 100 OR MORE FIRE SPRINKLERS WILL BE |
| | REQUIRED. |
| | |
| | 7) EXT BLD CODE 912.8 ACCESSIBLITY EXISTING BUILDINGS |
| | OR PORTIONS THEREOF THAT UNDERGO A CHANGE OF OCCUPANCY |
| | CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE FL |
| | BLD CODE. 11-4.1.6 ACCESSIBLE BUILDINGS: ALTERATIONS.1) |
| | GENERAL. ALTERATIONS TO EXISTING BUILDINGS AND |
| | FACILITIES SHALL COMPLY WITH THE FOLLOWING: |
| | (A) NO ALTERATION SHALL BE UNDERTAKEN WHICH DECREASES |
| | OR HAS THE EFFECT OF DECREASING ACCESSIBILITY OR |
| | USABILITY OF A BUILDING OR FACILITY BELOW THE |
| | REQUIREMENTS FOR NEW CONSTRUCTION AT THE TIME OF |
| | ALTERATION. |
| | |
| | 7A) SEE ENTRY TO RESTROOMS: 11-4.13.7 TWO DOORS IN |
| | SERIES. THE MINIMUM SPACE BETWEEN TWO HINGED OR PIVOTED |
| | DOORS IN SERIES SHALL BE 48 INCHES (1219 MM) PLUS THE |
| | WIDTH OF ANY DOOR SWINGING INTO THE SPACE. DOORS IN |
| | SERIES SHALL SWING EITHER IN THE SAME DIRECTION OR AWAY |
| | FROM THE SPACE BETWEEN THE DOORS [SEE FIGURE 26(A)]. |
| | |
| | 7B) NEW DOORS TO KITCHEN AND OFFICE AREAS NEED TO |
| | COMPLY WITH: 1-4.13.5 CLEAR WIDTH. DOORWAYS SHALL HAVE |
| | A MINIMUM CLEAR OPENING OF 32 INCHES (813 MM) WITH THE |
| | DOOR OPEN 90 DEGREES, MEASURED BETWEEN THE FACE OF THE |
| | DOOR AND THE OPPOSITE STOP. |
| | |
| | 7C) PLANS DO NOT INDICATE ANY COMPLIANCE WITH 11-4.32. |
| | 11-4.32.2 SEATING. IF SEATING SPACES FOR PEOPLE IN |
| | WHEELCHAIRS ARE PROVIDED AT FIXED TABLES OR COUNTERS, |
| | CLEAR FLOOR SPACE COMPLYING WITH SECTION 11-4.2.4 SHALL |
| | BE PROVIDED. SUCH CLEAR FLOOR SPACE SHALL NOT OVERLAP |
| | KNEE SPACE BY MORE THAN 19 INCHES (485 MM) (SEE FIGURE |
| | 45). |
| | |
| | ALL FIXED SEATING IN PUBLIC FOOD SERVICE |
| | ESTABLISHMENTS, IN ESTABLISHMENTS LICENSED UNDER THE |
| | BEVERAGE LAW FOR CONSUMPTION ON THE PREMISES, AND IN |
| | ALL OTHER FACILITIES GOVERNED BY REFERENCE SECTION |
| | 11-4.1 SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE |
| | WITH THE FOLLOWING REQUIREMENTS: |
| | |
| | (1) ALL AISLES ADJACENT TO FIXED SEATING SHALL PROVIDE |
| | CLEAR FLOOR SPACE FOR WHEELCHAIRS. |
| | |
| | (2) WHERE THERE ARE OPEN POSITIONS ALONG BOTH SIDES OF |
| | SUCH AISLES, THE AISLES SHALL BE NOT LESS THAN 52 |
| | INCHES (1321 MM) WIDE. |
| | |
| | 11-4.32.3 KNEE CLEARANCES. IF SEATING FOR PEOPLE IN |
| | WHEELCHAIRS IS PROVIDED AT TABLES OR COUNTERS, KNEE |
| | SPACES AT LEAST 27 INCHES (685 MM) HIGH, 30 INCHES (760 |
| | MM) WIDE, AND 19 INCHES (485 MM) DEEP SHALL BE PROVIDED |
| | (SEE FIGURE 45). |
| | |
| | 11-4.32.4 HEIGHT OF TABLES OR COUNTERS. THE TOPS OF |
| | ACCESSIBLE TABLES AND COUNTERS SHALL BE FROM 28 INCHES |
| | TO 34 INCHES (710 MM TO 865 MM) ABOVE THE FINISH FLOOR |
| | OR GROUND. |
| | |
| | 8A) PLANS DO NOT INCLUDE ANY MECHANICAL PLANS FOR THE |
| | PLACEMENT OF A/C AIR HANDLIER, COMPRESSOR OR THE |
| | CONDENSOR FOR THE MOVED WALK IN COOLER. PLEASE INDICATE |
| | COMPLIANCE WITH MECH. 301.13 WIND RESISTANCE MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE |
| | DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES ON |
| | THE EQUIPMENT & THE SUPPORTS AS DETERMINED IN |
| | ACCORDANCE WITH THE FL BLD CODE. THIS MAY BE ACCOMP |
| | LISHED BY DESIGN OR BY APPLICATION OF SECTION 301.13.1. |
| | |
| | 8B) 1511.7 ROOF MOUNTED MECHANICAL UNITS SHALL BE |
| | MOUNTED ON CURBS RAISED A MINIMUM OF 8 INCHES ABOVE THE |
| | ROOF SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH |
| | THE UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A |
| | MINIMUM CLEARENCE HEIGHT IN ACCORDANCE WITH TABLE |
| | 1511.7. |
| | |
| | 9) THE PERMIT APPLICATION INDICATES A VALUE OF 13,000 |
| | DOLLARS FOR THE WORK TO BE COMPLETED UNDER THIS |
| | CONTRACT, THE PLUMBING ALONE WILL COST MORE THAN WHAT |
| | IS INDICATED. PLEASE PROVIDE THE TOTAL VALUE, FAIR |
| | MARKET VALUE FOR THE PROJECT. |
| | |
| | W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. |
| | ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, |
| | AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, |
| | A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| | ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| | APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |