| Notes |
| Date |
Text |
| 2009-10-21 19:45:17 | ***PROVISO*** | | | | | | REVISION REQUIRED PRIOR TO ROUGH INSPECTION: | | | | | | 1. SHOW FIRE DAMPERS AT SUPPLY AND RETURN DUCT | | | PENETRATIONS OF 2-HOUR RATED WALL IN ACCORDANCE WITH | | | FBC-M 607.5.2 AND FBC-M 607.8. | | | | | | 2. SHOW SIZES OF ALL SUPPLY FLEXIBLE DUCTS ON PLANS IN | | | ACCORDANCE WITH FBC-M 603.1 AND FBC-B 13-410.AB.1.2. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|