Plan Review Notes
Plan Review Notes For Permit 09100371
Permit Number 09100371
Review Stop M
Sequence Number 1
Notes
Date Text
2009-10-21 19:45:17***PROVISO***
  
 REVISION REQUIRED PRIOR TO ROUGH INSPECTION:
  
 1. SHOW FIRE DAMPERS AT SUPPLY AND RETURN DUCT
 PENETRATIONS OF 2-HOUR RATED WALL IN ACCORDANCE WITH
 FBC-M 607.5.2 AND FBC-M 607.8.
  
 2. SHOW SIZES OF ALL SUPPLY FLEXIBLE DUCTS ON PLANS IN
 ACCORDANCE WITH FBC-M 603.1 AND FBC-B 13-410.AB.1.2.
  