| 2009-12-02 10:46:28 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. PROVIDE A SITE PLAN SHOWING LOCATION OF PROPOSED |
| | IMPROVEMENT IN RELATION TO THE PROPERTY LINE, FBC R301. |
| | A COPY OF A SURVEY WAS SUBMITTED. PLEASE SHOW LOCATION |
| | OF PROPOSED IMPROVEMENT AND INCLUDE "SUN DECK" WITH |
| | DIMENSIONS (OVERALL SIZE AND DISTANCE TO PROPERTY |
| | LINES). |
| | |
| | 2. DECLARE WIND DESIGN CRITERIA FBC R 301; DECLARE WIND |
| | SPEED FBC R301.2.1 (MINIMUM 140MPH), EXPOSURE CATEGORY |
| | (APPEARS TO BE EXPOSURE C). ALSO PROVIDE BUILDING |
| | HEIGHT SO THAT COMPONENTS & CLADDING DESIGN PRESSURES |
| | CAN BE DETERMINED. |
| | |
| | 3. INFORMATION REGARDING THE ROOF WAS NOT PROVIDED. IF |
| | THIS IS AN EXISTING ROOF, PLEASE NOTE ON PLANS. |
| | |
| | 4. PROVIDE ELEVATION DESIGNATIONS (N,S,E OR W). PROVIDE |
| | COMPASS NORTH ON THE SITE PLAN. FBC*106, FBC301. |
| | |
| | 5. HOW WILL THE BLOCK INFILL TIE IN STRUCTURALLY TO THE |
| | EXISTING? SEE FBC R301.1, ALL PARTS SHALL BE |
| | CONSTRUCTED TO SAFELY SUPPORT ALL LOADS. |
| | |
| | 6. HOW HAVE YOU DETERMINED THAT THE FOOTER SIZE IS |
| | ADEQUATE? |
| | |
| | 7. IMPACT FEES MAY BE DUE TO PALM BEACH COUNTY. THE |
| | PLANS MUST BE STAMPED AND THE RECEIPT (IF FEES ARE DUE) |
| | IS TO BE ATTACHED TO THE APPLICATION. |
| | |
| | 8. WILL THIS AREA BE AIR CONDITIONED? ENERGY CALCS MAY |
| | BE REQUIRED FBC R11. |
| | |
| | 9. PLEASE REVISE THE PLAN TO SHOW THAT THE MASTER |
| | BEDROOM EMERGENCY EGRESS IS NOT AFFECTED BY THE |
| | PROPOSED IMPROVEMENT, FBC R310 (YOU MAY DO THIS BY |
| | NOTING LOCATION OF MASTER BEDROOM EMERGENCY EGRESS ON |
| | THE PLAN). |
| | |
| | 10. PHOTOGRAPHS WERE INCLUDED IN THE PLANS. SEE |
| | FBC*106, PLANS ARE TO BE ARCHITECTURAL QUALITY, TO |
| | SCALE. PHOTOGRAPHS SHOULD NOT BE USED TO SHOW CODE |
| | COMPLIANCE. PLEASE INCORPORATE ANY REQUIRED INFORMATION |
| | INTO THE PLAN. |
| | |
| | 11.PORTIONS OF TWO DIFFERENT DOOR PRODUCT APPROVALS |
| | WERE PROVIDED. OTHER SHEETS STAPLED WITH THE ANCHOR |
| | EVALUATION REPORT WERE SPEC SHEETS FOR WINDOWS, DOORS, |
| | WINDOW INSTALLATION INFORMATION. PLEASE INCLUDE THE |
| | FLORIDA STATE PRODUCT APPROVAL COVER SHEET (SHOWS CODE |
| | VERSION, STATUS). FAC0B72. PLEASE PRINT THE COVER |
| | SHEET, EVALUATION REPORT, INSTALLATION INSTRUCTIONS FOR |
| | THE PRODUCT YOU WISH TO INSTALL. (PARTS OF FL8838, |
| | FL5262 INCLUDED, PLEASE SELECT ONE AND PRINT REQUIRED |
| | DOCUMENTS.) |
| | |
| | |
| | |
| | |
| | |
| | |