| Date |
Text |
| 2009-11-09 17:25:18 | |
| | |
| | PASSED/PROVISO |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. SHT A-2 EQUIPMENT PLAN. PLEASE VERIFY ALL EQUIPMENT |
| | WITH THE EQUIPMENT LEGEND. EXAMPLE NUMBER 26 IS |
| | INDICATED AS A CUBE ICE MACHINE IN THE LEGEND, BUT |
| | LOOKS LIKE A RANGE ON THE FLOOR PLAN. PLEASE IDENTIFY |
| | ALL EQUIPMENT ON THE FLOOR PLAN AND INDICATE AMOUNT ON |
| | THE LEGEND. THE LEGEND AND THE FLOOR PLAN SHALL REFLECT |
| | EACH OTHER. SECTION 106.1.1. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. SHT P-1 SHOWS 2 |
| | NUMBER 27'S THAT ARE INDICATED AS TURBO-FLOW CONVECTION |
| | OVENS ON SHT A-2 BUT INDICATED AS FRYERS ON THE GAS |
| | ISOMETRIC RISER DIAGRAM. ALSO SHT A-2 SHOWS THE FRYERS |
| | ON THE WEST WALL NOT IN LINE WITH THE RANGE. PLEASE |
| | IDENTIFY ALL EQUIPMENT ON THE FLOOR PLAN AND INDICATE |
| | THE AMOUNT ON THE LEGEND. |
| | |
| | 2. SHT A-2 ITEM 7 IS INDICATED AS A WATER FILTER. THE |
| | FILTER SHALL MEET THE REQUIREMENTS OF NSF-42 OR NSF-58 |
| | DEPENDING ON THE REQUIRMENTS OF SECTIONS 611.1 OR 611.2 |
| | WHICH EVER SECTION APPLIES. PLEASE SUBMIT MANUF. |
| | SPECIFICATIONS FOR FILTER. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 3. SHT A-3 SHOW COMPLIANCE WITH THE FOLLOWING: |
| | |
| | ___FOR W/C'S: |
| | A. OK |
| | B. OK |
| | |
| | ___FOR LAVS: |
| | A. OK |
| | B. 11-4.19.3 CLEAR FLOOR SPACE |
| | ****NOT ADDRESSED. |
| | C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | ****NOT ADDRESSED. |
| | D. OK |
| | |
| | REVISION REQUIRED FOR SHEETS A-2 & A-3 SHOWING |
| | REQUIREMENTS. |
| | |
| | |
| | |
| | |
| | |
| | . |