Plan Review Notes
Plan Review Notes For Permit 09100323
Permit Number 09100323
Review Stop P
Sequence Number 2
Notes
Date Text
2009-11-09 17:25:18 
  
 PASSED/PROVISO
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT A-2 EQUIPMENT PLAN. PLEASE VERIFY ALL EQUIPMENT
 WITH THE EQUIPMENT LEGEND. EXAMPLE NUMBER 26 IS
 INDICATED AS A CUBE ICE MACHINE IN THE LEGEND, BUT
 LOOKS LIKE A RANGE ON THE FLOOR PLAN. PLEASE IDENTIFY
 ALL EQUIPMENT ON THE FLOOR PLAN AND INDICATE AMOUNT ON
 THE LEGEND. THE LEGEND AND THE FLOOR PLAN SHALL REFLECT
 EACH OTHER. SECTION 106.1.1.
 ****NO RESPONSE, COMMENT NOT ADDRESSED. SHT P-1 SHOWS 2
 NUMBER 27'S THAT ARE INDICATED AS TURBO-FLOW CONVECTION
 OVENS ON SHT A-2 BUT INDICATED AS FRYERS ON THE GAS
 ISOMETRIC RISER DIAGRAM. ALSO SHT A-2 SHOWS THE FRYERS
 ON THE WEST WALL NOT IN LINE WITH THE RANGE. PLEASE
 IDENTIFY ALL EQUIPMENT ON THE FLOOR PLAN AND INDICATE
 THE AMOUNT ON THE LEGEND.
  
 2. SHT A-2 ITEM 7 IS INDICATED AS A WATER FILTER. THE
 FILTER SHALL MEET THE REQUIREMENTS OF NSF-42 OR NSF-58
 DEPENDING ON THE REQUIRMENTS OF SECTIONS 611.1 OR 611.2
 WHICH EVER SECTION APPLIES. PLEASE SUBMIT MANUF.
 SPECIFICATIONS FOR FILTER.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 3. SHT A-3 SHOW COMPLIANCE WITH THE FOLLOWING:
  
 ___FOR W/C'S:
 A. OK
 B. OK
  
 ___FOR LAVS:
 A. OK
 B. 11-4.19.3 CLEAR FLOOR SPACE
 ****NOT ADDRESSED.
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 ****NOT ADDRESSED.
 D. OK
  
 REVISION REQUIRED FOR SHEETS A-2 & A-3 SHOWING
 REQUIREMENTS.
  
  
  
  
  
 .