| Plan Review Notes For Permit 09100323 |
| Permit Number |
09100323 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-11-17 11:24:06 | ***PROVISO*** | | | 1. REVISION REQUIRED: PROVIDE MOTIRIZED AND GRAVITY | | | OPERATED (BACKDRAFT) DAMPERS AS NECESSARY TO ENSURE ALL | | | REQUIRED OUTDOOR AIR FOR KSF-1 AND BOTH AIR HANDLERS IS | | | BEING SUPPLIED ONLY FROM OUTDOORS RATHER THAN FROM | | | INDOORS THROUGH OTHER ATTACHED DUCTS. ALL VENTILATION | | | AIR SHALL BE DIRECTLY FROM THE OUTDOORS IN ACCORDANCE | | | WITH FBC-M 401.4 AND FBC-M 403.2. | | | | | | 2. REVISION REQUIRED: PROVIDE MANUFACTURER'S WIND | | | RESISTANCE DATA FOR ALL APPLIANCES EXPOSED TO WIND IN | | | ACCORDANCE WITH FBC-M 301.12. | | | | | | 3. PAGE M-3: CENTRIFUGAL KITCHEN EXHAUST FAN SHALL BE | | | ORIENTED TO DISCHARGE VERTICALLY IN ACCORDANCE WITH | | | FBC-M 506.3.12. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|