2009-10-27 08:16:33DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 11
 MUNICIPAL CODE WPB
  
 1. SHT A-2 EQUIPMENT PLAN. PLEASE VERIFY ALL EQUIPMENT
 WITH THE EQUIPMENT LEGEND. EXAMPLE NUMBER 26 IS
 INDICATED AS A CUBE ICE MACHINE IN THE LEGEND, BUT
 LOOKS LIKE A RANGE ON THE FLOOR PLAN. PLEASE IDENTIFY
 ALL EQUIPMENT ON THE FLOOR PLAN AND INDICATE AMOUNT ON
 THE LEGEND. THE LEGEND AND THE FLOOR PLAN SHALL REFLECT
 EACH OTHER. SECTION 106.1.1.
  
 2. SHT A-2 ITEM 7 IS INDICATED AS A WATER FILTER. THE
 FILTER SHALL MEET THE REQUIREMENTS OF NSF-42 OR NSF-58
 DEPENDING ON THE REQUIRMENTS OF SECTIONS 611.1 OR 611.2
 WHICH EVER SECTION APPLIES. PLEASE SUBMIT MANUF.
 SPECIFICATIONS FOR FILTER.
  
 3. SHT A-3 SHOW COMPLIANCE WITH THE FOLLOWING:
  
 ___FOR W/C'S:
 A. 11-4.16.4 GRAB BARS
 B. 11-4.16.5 FLUSH CONTROLS
  
 ___FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS.
  
 4. SHTS P-1 & P-2 ALL FLOOR DRAINS, FLOOR SINKS OR
 PLUMBING FIXTURES THAT DRAIN GREASE LADEN WASTE SHALL
 CONNECT TO THE GREASE INTERCEPTOR. SECTION 1003.1.
  
 5. PER TABLE 403.1 A SERVICE SINK IS REQUIRED. PLEASE
 INDICATE THE LOCATION OF THE EXISTING SERVICE SINK OR
 SHOW THE NEW REQUIRED SERVICE SINK. THE SERVICE SINK
 SHALL ALSO CONNECT TO THE GREASE WASTE SYSTEM. SECTION
 1003.1.
  
 6. SHTS P-1 & P-2 SANITARY ISOMETRIC RISER. EVERY DRY
 VENT CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT
 ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE.
 SECTION 905.3. EVERY DRY VENT SHALL RISE VERTICALLY TO
 A MINIMUM 6 INCHES ABOVE THE FLOOD LEVEL RIM OF THE
 HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. SECTION
 905.4. THE 3 INCH VTR IS A DRY HORIZONTAL VENT AND DOES
 NOT MEET THE CODE REQUIREMENTS.
  
 7. SHT P-2 DOMESTIC WATER ISOMETRIC RISER. THE WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN
 AN "EFFECTIVE RANGE", NOT IN THE CEILING AS INDICATED.
 PDI-WH 201.
  
 8. SHT P-3 SYMBOL LEGEND FOR THE WATER HAMMER ARRESTORS
 INDICATES "LETTER DENOTES PDI SIZE". THERE IS NO LETTER
 INDICATED ON THE DOMESTIC WATER ISOMETRIC.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.