| Date |
Text |
| 2009-10-27 08:16:33 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 11 |
| | MUNICIPAL CODE WPB |
| | |
| | 1. SHT A-2 EQUIPMENT PLAN. PLEASE VERIFY ALL EQUIPMENT |
| | WITH THE EQUIPMENT LEGEND. EXAMPLE NUMBER 26 IS |
| | INDICATED AS A CUBE ICE MACHINE IN THE LEGEND, BUT |
| | LOOKS LIKE A RANGE ON THE FLOOR PLAN. PLEASE IDENTIFY |
| | ALL EQUIPMENT ON THE FLOOR PLAN AND INDICATE AMOUNT ON |
| | THE LEGEND. THE LEGEND AND THE FLOOR PLAN SHALL REFLECT |
| | EACH OTHER. SECTION 106.1.1. |
| | |
| | 2. SHT A-2 ITEM 7 IS INDICATED AS A WATER FILTER. THE |
| | FILTER SHALL MEET THE REQUIREMENTS OF NSF-42 OR NSF-58 |
| | DEPENDING ON THE REQUIRMENTS OF SECTIONS 611.1 OR 611.2 |
| | WHICH EVER SECTION APPLIES. PLEASE SUBMIT MANUF. |
| | SPECIFICATIONS FOR FILTER. |
| | |
| | 3. SHT A-3 SHOW COMPLIANCE WITH THE FOLLOWING: |
| | |
| | ___FOR W/C'S: |
| | A. 11-4.16.4 GRAB BARS |
| | B. 11-4.16.5 FLUSH CONTROLS |
| | |
| | ___FOR LAVS: |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | B. 11-4.19.3 CLEAR FLOOR SPACE |
| | C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | D. 11-4.19.5 FAUCETS. |
| | |
| | 4. SHTS P-1 & P-2 ALL FLOOR DRAINS, FLOOR SINKS OR |
| | PLUMBING FIXTURES THAT DRAIN GREASE LADEN WASTE SHALL |
| | CONNECT TO THE GREASE INTERCEPTOR. SECTION 1003.1. |
| | |
| | 5. PER TABLE 403.1 A SERVICE SINK IS REQUIRED. PLEASE |
| | INDICATE THE LOCATION OF THE EXISTING SERVICE SINK OR |
| | SHOW THE NEW REQUIRED SERVICE SINK. THE SERVICE SINK |
| | SHALL ALSO CONNECT TO THE GREASE WASTE SYSTEM. SECTION |
| | 1003.1. |
| | |
| | 6. SHTS P-1 & P-2 SANITARY ISOMETRIC RISER. EVERY DRY |
| | VENT CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT |
| | ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE. |
| | SECTION 905.3. EVERY DRY VENT SHALL RISE VERTICALLY TO |
| | A MINIMUM 6 INCHES ABOVE THE FLOOD LEVEL RIM OF THE |
| | HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. SECTION |
| | 905.4. THE 3 INCH VTR IS A DRY HORIZONTAL VENT AND DOES |
| | NOT MEET THE CODE REQUIREMENTS. |
| | |
| | 7. SHT P-2 DOMESTIC WATER ISOMETRIC RISER. THE WATER |
| | HAMMER ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN |
| | AN "EFFECTIVE RANGE", NOT IN THE CEILING AS INDICATED. |
| | PDI-WH 201. |
| | |
| | 8. SHT P-3 SYMBOL LEGEND FOR THE WATER HAMMER ARRESTORS |
| | INDICATES "LETTER DENOTES PDI SIZE". THERE IS NO LETTER |
| | INDICATED ON THE DOMESTIC WATER ISOMETRIC. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |