| 2009-10-26 19:31:17 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. OUTSIDE AIR INTAKES FOR AIR HANDLERS AND KSF-1 ARE |
| | FACING AN ALLEY. MECHANICAL OUTDOOR AIR INTAKE OPENINGS |
| | SHALL BE LOCATED A MINIMUM OF 10 FEET HORIZONTALLY FROM |
| | ANY HAZARDOUS OR NOXIOUS CONTAMINANT SOURCE, SUCH AS |
| | STREETS, ALLEYS AND PARKING LOTS AND LOADING DOCKS IN |
| | ACCORDANCE WITH FBC-M 401.4.1. SELECT AN ALTERNATE |
| | LOCATION WHICH MEETS THE REQUIREMENTS OF THIS SECTION. |
| | |
| | 2. FLOOR PLANS SHOW A 20X20 HOOD SUPPLY, 14X14 OUTSIDE |
| | AIR, 6 INCH ROUND EXHAUST AND 4 INCH ROUND FLUE |
| | PENETRATING A FIRE-RESISTANCE RATED WALL ASSEMBLY WITH |
| | NO PROTECTION. SHOW HOW THESE DUCT PENETRATIONS OF THE |
| | RATED WALL ARE TO BE PROTECTED IN ACCORDANCE WITH FBC-M |
| | 607.5, FBC-M 607.8 AND FBC-FG 302.2. |
| | |
| | 3. A METHOD A CODE COMPLIANCE FORM HAS BEEN SUBMITTED. |
| | HOWEVER, IF THIS SCOPE OF WORK DOES NOT CONSTITUTE A |
| | RENOVATION (SEE DEFINITIONS FBC-B SECTION 13-202) THEN |
| | DEMONSTRATION OF COMPLIANCE WITH FBC-B 13-101.6 IS |
| | REQUIRED WHERE NEW PRODUCTS ARE INSTALLED OR REPLACED |
| | IN EXISTING BUILDINGS. ALTERNATIVELY, IF THIS SCOPE OF |
| | WORK CONSTITUTES A CHANGE OF OCCUPANCY (THERE IS NO |
| | INDICATION ON PLANS OR PERMIT APPLICATION), THIS WORK |
| | SHALL MEET THE REQUIREMENTS FOR RENOVATIONS IN SECTION |
| | 101.1.3 FOR THOSE COMPONENTS WHICH ARE BEING |
| | RETROFITTED OR REPLACED IN ACCORDANCE WITH FBC-B |
| | 13-101.3.1. |
| | |
| | 4. PAGE M-1 SHOWS NEW CONDENSERS ON STANDS TO BE |
| | INSTALLED ON THE ROOF. NO INFORMATION WAS PROVIDED |
| | REGARDING THE STANDS OR THE INSTALLATION OF THE NEW |
| | APPLIANCES FOR WIND RESISTANCE. IF PRE-ENGINEERED A/C |
| | STANDS ARE USED, SUBMIT PRODUCT APPROVALS FOR THE |
| | STANDS IN ACCORDANCE WITH FBC-B 106.3.3. ALSO, PROVIDE |
| | PRODUCT APPROVAL FOR WALL LOUVERS PER THIS SECTION |
| | UNLESS THE LOUVER IS ELIMINTAED IN CONJUNCTION WITH |
| | COMMENT #1 ABOVE. |
| | |
| | 5. PROVIDE MANUFACTURER'S DATA SHOWING ALL OUTDOOR |
| | APPLIANCES ARE DESIGNED FOR WIND RESISTANCE IN |
| | ACCORDANCE WITH FBC-M 301.12. WHEN APPLYING FOR |
| | SEPARATE HOOD PERMIT, INCLUDE WIND RESISTANCE DATA FOR |
| | KITCHEN EXHAUST FAN AND ENGINEERED INSTALLATION DETAILS |
| | FOR THE FAN AND EXTERIOR DUCT SUPPORTS. |
| | |