2009-10-26 19:31:17REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. OUTSIDE AIR INTAKES FOR AIR HANDLERS AND KSF-1 ARE
 FACING AN ALLEY. MECHANICAL OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FEET HORIZONTALLY FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT SOURCE, SUCH AS
 STREETS, ALLEYS AND PARKING LOTS AND LOADING DOCKS IN
 ACCORDANCE WITH FBC-M 401.4.1. SELECT AN ALTERNATE
 LOCATION WHICH MEETS THE REQUIREMENTS OF THIS SECTION.
  
 2. FLOOR PLANS SHOW A 20X20 HOOD SUPPLY, 14X14 OUTSIDE
 AIR, 6 INCH ROUND EXHAUST AND 4 INCH ROUND FLUE
 PENETRATING A FIRE-RESISTANCE RATED WALL ASSEMBLY WITH
 NO PROTECTION. SHOW HOW THESE DUCT PENETRATIONS OF THE
 RATED WALL ARE TO BE PROTECTED IN ACCORDANCE WITH FBC-M
 607.5, FBC-M 607.8 AND FBC-FG 302.2.
  
 3. A METHOD A CODE COMPLIANCE FORM HAS BEEN SUBMITTED.
 HOWEVER, IF THIS SCOPE OF WORK DOES NOT CONSTITUTE A
 RENOVATION (SEE DEFINITIONS FBC-B SECTION 13-202) THEN
 DEMONSTRATION OF COMPLIANCE WITH FBC-B 13-101.6 IS
 REQUIRED WHERE NEW PRODUCTS ARE INSTALLED OR REPLACED
 IN EXISTING BUILDINGS. ALTERNATIVELY, IF THIS SCOPE OF
 WORK CONSTITUTES A CHANGE OF OCCUPANCY (THERE IS NO
 INDICATION ON PLANS OR PERMIT APPLICATION), THIS WORK
 SHALL MEET THE REQUIREMENTS FOR RENOVATIONS IN SECTION
 101.1.3 FOR THOSE COMPONENTS WHICH ARE BEING
 RETROFITTED OR REPLACED IN ACCORDANCE WITH FBC-B
 13-101.3.1.
  
 4. PAGE M-1 SHOWS NEW CONDENSERS ON STANDS TO BE
 INSTALLED ON THE ROOF. NO INFORMATION WAS PROVIDED
 REGARDING THE STANDS OR THE INSTALLATION OF THE NEW
 APPLIANCES FOR WIND RESISTANCE. IF PRE-ENGINEERED A/C
 STANDS ARE USED, SUBMIT PRODUCT APPROVALS FOR THE
 STANDS IN ACCORDANCE WITH FBC-B 106.3.3. ALSO, PROVIDE
 PRODUCT APPROVAL FOR WALL LOUVERS PER THIS SECTION
 UNLESS THE LOUVER IS ELIMINTAED IN CONJUNCTION WITH
 COMMENT #1 ABOVE.
  
 5. PROVIDE MANUFACTURER'S DATA SHOWING ALL OUTDOOR
 APPLIANCES ARE DESIGNED FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.12. WHEN APPLYING FOR
 SEPARATE HOOD PERMIT, INCLUDE WIND RESISTANCE DATA FOR
 KITCHEN EXHAUST FAN AND ENGINEERED INSTALLATION DETAILS
 FOR THE FAN AND EXTERIOR DUCT SUPPORTS.
  