| 2009-10-27 08:23:17 | DENIED |
| | REFERENCE: |
| | FBC-2007 FUEL GAS |
| | |
| | A. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE |
| | FOLLOWING INFORMATION REQUIRED FOR GAS PERMIT: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR |
| | 2007 FUEL GAS CODE. -- NOT ALL SECTIONS INDICATE CUT |
| | SECTIONS. SEE HORIZONTAL SECTION FROM METER, FIRST |
| | VERTICAL RISER, SECTION AFTER FIRST TEE TO OVEN AND |
| | SECTION AFTER SECOND TEE TO FRYERS & RANGE, OFFSET & |
| | DROP TO WATER HEATER, SECTIONS BETWEEN FRYERS & BETWEEN |
| | LAST FRYER & RANGE & OFFSET & DROP TO THE OVEN. |
| | |
| | 2. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2007 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). -- TO BE VERIFIED WHEN |
| | COMMENT NUMBER ONE IS ADDRESSED. |
| | |
| | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE |
| | SEC. G2413.2. |
| | |
| | 4. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |