| 2009-10-26 11:47:20 | *****DENIED***** |
| | |
| | |
| | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHAL;L COMPLY WITH NFPA 241 - |
| | 2004 EDITION. |
| | |
| | 2. THE ADDRESS LISTED IN THE SUBMITTED PLANS (403 |
| | NORTHWOOD ROAD) DO NOT CORRELATE WITH THAT LISTED ON |
| | THE APPLICATION AND/OR IN OUR PERMITTING SYSTEM (401 |
| | NORTHWOOD ROAD). THE ACTUAL PROJECT SITE ADDRESS SHALL |
| | BE INCLUDED IN THE TITLE BLOCK OF EACH SUBMITTTED PLAN |
| | SHEET. |
| | |
| | 3. THE 2006 EDITION OF NFPA 101 - LIFE SAFETY CODE - |
| | SHALL BE REFERENCED. |
| | |
| | 4. THE WIDTH OF ANY EXIT ACCESS CORRIDOR SERVING 50 OR |
| | MORE PERSONS SHALL NOT BE LESS THAN 44 INCHES. |
| | |
| | 5. THE WIDTH OF AISLE SERVING SEATING AST TABLESSHALL |
| | NOT BE LESS THAN 44 INCHES WHERE SERVING AN OCCUPANT |
| | LOAD OF EXCEEDING 50 PERSONS. |
| | |
| | 6. SPECIFY INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR |
| | CLASS II. |
| | |
| | 7. SHOW THE LOCATION OF THE FIRE EXTINGUISHERS WHICH |
| | SATISFY THE 75' TRAVEL DISTANCE. |
| | |
| | 8. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS. THESE |
| | MAY BE SHOWN ON THE CEILING PLAN (SHEET A-4). |
| | |
| | 9. ON SHEET A-1, THERE APPEARS TO BE TWO WEST DOORS |
| | THAT ACCESS THE EXISTING EXIT CORRIDOR, HOWEVER ONLY |
| | ONE SUCH DOOR IS SHOWN ON SHEET E-2. PLEASE EXPLAIN. |
| | |
| | |
| | TO EXPEDIT THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |