| 2009-10-26 17:35:54 | |
| | |
| | APPLICATION #09100323 ELECTRICAL PLAN REVIEW |
| | 403 NORTHWOOD ROAD 10/26/09 |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005 |
| | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} PLEASE INDICATE THE CODE CYCLE THIS PROJECT WAS |
| | DESIGNED UNDER. 2005 NEC, 2006 NFPA 101 ADD TO NOTES |
| | FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3 |
| | FBC AS AMENDED. |
| | |
| | 2} SHEET E-1 ROOF POWER PLAN DOES NOT INDICATE THE |
| | RECEPTACLE REQUIRED BY 210.63, LOCATE SAME ON PLAN. |
| | |
| | 3} NOTE #1 INCORRECTLY SITES 210.8(B)(3), SHOULD SITE |
| | 210.8(B)(2). |
| | |
| | 4}THE LIGHTING DENSITY CALCULATIONS SHEET E-2, SITE |
| | TABLE 415.2.B, THAT IS A REFERENCE FROM THE 2004 FBC. |
| | THE 2007 FBC IS CURRENT AND 415.B.1 IS THE TABLE |
| | CURRENTLY BEING USED, CORRECT SAME. |
| | |
| | 5} SHEET E-2 FIXTURE LEGEND SCHEDULE NOTE #3 |
| | INCORRECTLY 410.73(G), THIS ARTICLE IS FROM THE 2005 |
| | NEC, THE CURRENT 2008 ARTICLE IS 410.130(G)(1), PLEASE |
| | CORRECT AND CHECK ALL NOTES AND REFERENCES FOR THE |
| | CORRECT CODE CYCLES. |
| | |
| | 6} THE RISER DIAGRAM LEGEND ON SHEET E-3 LISTS THE |
| | PANELS AS BEING 277/480 VOLTS IN VIOLATION OF 110.3(B). |
| | THE SERVICE IS 120/208 VOLTS. |
| | |
| | 7} NOTE # 28 REFERS SHEET E-3SPECIFICATIONS TO 480 VOLT |
| | DELTA SYSTEM COLOR CODE, THE SERVICE IS A 120/208 Y, |
| | CORRECT NOTE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER,CITY OF WEST PALM |
| | BEACH/561/805-6718 |
| | |
| | |