2009-10-20 07:55:38BUILDING PLAN REVIEW
 PERMIT: 09100323
 ADD: 401 NORTHWOOD RD
 CONT: G. FLEWELLING CONSTRUCTION
 TEL: (561)635-6935
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 OCT. 20/ 2009
 1ST REVIEW
 ACTION: DENIED
  
 1A) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 1B) ADDITIONAL INFORMATION REQUIRED106.1.2, IS THIS A
 CHANGE IN OCCUPANCY?
  
 2) SHEET A-1;
  
 2A) PLANS DO NOT INDICATE WHAT WALLS ARE EXISTING AND
 WHAT WALLS ARE NEW. 106.1.2 ADDITIONAL INFORMATION
 REQUIRED. IT APPEARS THERE IS A SHARED EXIT ACCESS
 CORRIDOR SHARED BY A MINIMUM OF TWO TENANTS,( 2007
 EXIST BLDG CODE 705.2 EXCEPTION 2) THE NEW OPENING FROM
 THIS TENANT SPACE DOES NOT INDICATE IF THE CORRIDOR
 CONTINUES TO A THIRD TENANT. IF SO PLEASE REVIEW
 SECTION 1005 .2 OF THE FBC. DOOR ENCROACHMENT.
  
 2B) PLEASE PROVIDE ADDITIONAL INFORMATION AS TO THE
 OBJECT (2'-0"X 5'-6") DIRECT IN FRONT OF THE RESTROOMS
 IT APPEARS TO BE BLOCKING THE EGRESS PATH. 11-4.3.3
 THTE MINIMUM CLEAR WIDTH OF AN ACCESSIBLE ROUTE IS
 36".11-5.3.
  
 2C) PLEASE PROVIDE COMLIANCE WITH :11-5.1 GENERAL.
 EXCEPT AS SPECIFIED OR MODIFIED IN THIS SECTION,
 RESTAURANTS AND CAFETERIAS SHALL COMPLY WITH THE
 REQUIREMENTS OF SECTION 11-4.1 TO SECTION 11-4.35.
 WHERE FIXED TABLES (OR DINING COUNTERS WHERE FOOD IS
 CONSUMED BUT THERE IS NO SERVICE) ARE PROVIDED, AT
 LEAST 5 PERCENT, BUT NOT LESS THAN ONE, OF THE FIXED
 TABLES (OR A PORTION OF THE DINING COUNTER) SHALL BE
 ACCESSIBLE AND SHALL COMPLY WITH SECTION 11-4.32 AS
 REQUIRED IN SECTION 11-4.1.3(18).
  
 2D) SHEET A-1 DOES NOT PROVIDE A DETAIL FOR THE FRONT
 ENTRY PROVIDING EGRESS FOR HANDICAPPED PATRONS.
 11-4.1.6 (2) (A)(I) AN ACCESSIBLE ENTRANCE.
  
 2E) THE NEW EXIT ACCESS DOOR LEADING INTO THE COORIDOR
 IS INDICATED AS A "C" RATED DOOR, PLEASE REVIEW OPENING
 PROTECTIVES TABLE 715.4, OPENING PROTECTION IS IN HOURS
 AND MINUTES.
  
 3) SHEET M-1 INDICATES THE A/C CONDENSORS AND COOLER
 CONDENSOR TO BE LOCATED ON THE ROOF:
  
 3A) PRE-MANUFACTURED A/C STANDS: 06.3 PRODUCT APPROVALS
 SUBMITTED WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL, RULE 9B-72(C)(G). PLEASE PROVIDE PRODUCT
 APPROVALS (2 COPIES) FOR A/C STAND.
  
 3B) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 3C) ALL ROOFTOP EQUIPMEN NEEDS TO INDICATE COMPLIANCE
 WITH, 301.13 FBC MECHANICAL. WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST WIND PRESSURES ON THE EQUIPMENT AND THE SUPPORTS
 AS DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING. THIS IS THE EQUIPMENT EXTERIOR SHELL AS
 WELL AS THE TIE DOWN TO THE A/C STAND AS WELL AS THE
 HOOD EXHAUST DUCT AND EXHAUST FAN.
  
 3D) THE INTAKE DUC , WALL LOUVER WILL ALSO NEED TO
 PROVIDE PRODUCT APPROVAL (2 COPIES) FOR WIND, RULE
 9B-72#1)(C).
  
 4) NOTE ENERGY CALCULATION METHOD "A" NOT REQUIRED BY
 BUILDING , NOT REVIEWED.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved