Plan Review Notes
Plan Review Notes For Permit 09100254
Permit Number 09100254
Review Stop I
Sequence Number 1
Notes
Date Text
2009-10-30 14:47:421. ENTIRE INSTALLATION TO COMPLY WITH NFPA 72, THE
 NATIONAL FIRE ALARM CODE.
  
 2. PLEASE INDICATE IN WRITING WHAT THE VOICE EVACUATION
 PORTION OF THE FIRE ALARM SYSTEM WILL SAY.
  
 3. THE NEW FIRE ALARM SYSTEM AT BB KING SHALL BE
 INSPECTED, TESTED, AND APPROVED BY THE BUREAU OF FIRE
 PREVENTION.
  
 4. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF AT
 LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS.
  
 5, ACTIVATION OF THE HOOD SUPPRESSION SYSTEM SHALL
 CAUSE THE ACTIVATION OF THE FIRE ALARM SYSTEM.
  
 6. THE ACTIVATION OF ANY FIRE ALARM EQUIPMENT WITHIN C
 BLOCK SHALL CAUSE THE FIRE ALARM SYSTEM EQUIPMENT TO
 ACTIVATE IN BB KING.
  
 7. THE FIRE ALARM AND FIRE SPRINKLER SYSTEM SHALL BE
 MONITORED BY A UL LISTED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 8. ENTIRE INSTALLATION IS SUBJECT TO FIELD INSPECTION
 AND APPROVAL.
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 BUREAU OF FIRE PREVENTION
 500 NORTH DIXIE HIGHWAY
 WEST PALM BEACH, FLORIDA 33401
 (561) 804-4709 PHONE
 (561) 804-4774 FAX
 [email protected]