| Date |
Text |
| 2009-10-22 18:09:39 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 11 |
| | MUNICIPAL CODE W.P.B. |
| | |
| | 1. SHT A2.1 MEN'S TOILET ROOM. THE LAV IN THE |
| | ACCESSIBLE STALL APPEARS TO RESTRICT THE ACCESS TO THE |
| | STALL. PLEASE MOVE THE LAV SO THAT THE W/C IS JUST |
| | OUTSIDE THE CLEAR FLOOR SPACE REQUIRED FOR THE LAV. |
| | SECTION 11-4.17.3 EXCEPTION (TECHNICALLY INFEASIBLE) TO |
| | BRING THE STALL UP TO AS MUCH CODE REQUIREMENTS AS |
| | POSSIBLE. |
| | |
| | 2. SHTS P1.01 & P2.01 THE GREASE INTERCEPTOR SHALL BE |
| | SIZED & APPROVED BY THE UTILITY DEPT. ENVIRONMENTAL |
| | COMPLIANCE. PLEASE CONTACT HOLLY MCGRATH, LABORATORY |
| | SUPERVISOR. PHONE NUMBER (561) 822-2271, FAX (561) |
| | 822-2279 OR E-MAIL [email protected]. A DETERMINATION |
| | FROM THE UTILITY DEPT. IS REQUIRED IN WRITING OR E-MAIL |
| | PRIOR TO PERMIT. ARTICLE III SECTION 90-124(7). |
| | |
| | 3. SHTS P1.01 & P2.01 ALL FLOOR DRAINS & THE FLOOR SINK |
| | FOR THE 3 COMPARTMENT SINK IN THE FOOD PREP AREA AS |
| | WELL AS THE HAND SINK IN THE FOOD PREP AREA SHALL DRAIN |
| | THROUGH THE REQUIRED GREASE INTERCEPTOR. SECTION |
| | 1003.3.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |