| 2009-10-14 10:39:43 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. PROVIDE ARCHITECTURAL QUALITY PLANS CLEARLY SHOWING |
| | SCOPE OF WORK. FBC*106.1.1. CONSTRUCTION DOCUMENTS |
| | SHALL BE DIMENSIONED AND TO SCALE AND SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFIRM TO THE PROVISOINS OF THIS CODE AND |
| | RELEVANT LASW, ORDINANCES, RULES AND REGULATIONS. THE |
| | DRAWINGS SUBMITTED DO NOT CLEARLY SHOW SCOPE OF WORK; |
| | THIS SHOWS A NEW WALL, BUT NOTHING IN THE PLAN TO |
| | INDICATE SUCH. THE DRAWINGS DO NOT HAVE ANY STRUCTURAL |
| | INFORMATION AND DO NOT STATE WIND DESIGN CRITERIA FBC |
| | R301. PLEASE SUBMIT DRAWINGS WHICH CLEARLY SHOW SCOPE |
| | AND CODE COMPLIANCE. CERTIFICATION BY A DESIGN |
| | PROFESSIONAL OR CALCULATIONS JUSTIFYING DESIGN MAY BE |
| | REQUIRED. |
| | |
| | 2. TWO COMPLETE LEGIBLE IDENTICAL SETS OF PERMIT |
| | DOCUMENTS REQUIRED. ONLY ONE SET OF PRODUCT APPROVALS |
| | WERE SUBMITTED, AND MOST OF THE PRODUCT APPROVALS ARE |
| | ILLEGIBLE. THEY MAY BE AVAILABLE AT WWW.MIAMIDADE.GOV |
| | OR WWW.FLORIDABUILDING.ORG. 10/21/9 COMMENT REVISED - |
| | TOLD OWNER/BUILDER THAT LEGIBLE PRODUCT APPROVALS WOULD |
| | BE PROVIDED FOR HER DUE TO HER HARDSHIP (NO INTERNET |
| | ACCESS) |
| | |
| | 3. A MULLION PRODUCT APPROVAL WAS SUBMITTED, BUT NO |
| | MULLIONS SHOWN ON THE ELEVATION. PLEASE CLARIFY WHERE |
| | THIS WILL BE INSTALLED. SOMEONE HAS HAND WRITTEN "NON |
| | IMPACT" ON THE MULLION PRODUCT APPROVAL. THIS IS AN |
| | IMPACT PRODUCT. |
| | |
| | 4. PLANS STATE THAT DOORS AND WINDOWS WILL BE INSTALLED |
| | WITH TAPCONS. COMPONENTS AND CLADDING ARE TO BE |
| | INSTALLED AS PER PRODUCT APPROVAL OR MAY BE REVISED |
| | USING AN ENGINEER. |
| | |
| | 5. THE SHUTTER DOCUMENT IS ILLEGIBLE. FLORIDA STATE OR |
| | LOCAL PRODUCT APPROVAL IS REQUIRED, FAC9B72. TWO |
| | DIFFERENT DOCUMENTS WERE SUBMITTED. IF A MIAMIDADE NOA |
| | IS USED, THE FLORIDA STATE PRODUCT APPROVAL COVER SHEET |
| | IS NOT REQUIRED. IF THE OTHER DOCUMENT IS USED, IT |
| | APPEARS THAT MAY BE A FLORIDA STATE PRODUCT APPROVAL, |
| | AND THEN THE COVER SHEET IS REQUIRED AS IT GIVES THE |
| | PRODUCT APPROVAL NUMBER AND DOCUMENTS UNDER WHICH CODE |
| | THE PRODUCT HAS BEEN APPROVED. PLEASE PROVIDE. PLEASE |
| | SUBMIT TWO COPIES OF THE SAME PRODUCT APPROVAL, AND |
| | REMOVE THE EXTRA DOCUMENT. |
| | |
| | 6. FOR THE SHUTTERS, PLEASE COMPLETE THE SAMPLE |
| | INSTALLATION SCHEDULE OR PROVIDE ALL INFORMATION TO |
| | SHOW CODE COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC |
| | R301, FBC1609. TWO SETS REQUIRED. THIS FORM IS |
| | AVAILABLE IN THE LOBBY OR ON THE INTERNET AT |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ |
| | INSTALLATION.PDF |
| | |
| | 7. THE APPLICATION STATES THAT THE WALLS WILL BE BUILT |
| | ON EXISTING FOOTERS AND THAT THE WORK IS NON |
| | STRUCTURAL. HOW HAVE YOU DETERMINED THIS? TYPICALLY |
| | EXTERIOR FRAMED WOOD WALLS ARE BEARING WALLS. NO |
| | INFORMATION REGARDING THE "EXISTING FOOTING" WAS |
| | PROVIDED. HOW HAS IT BEEN DETERMINED THAT THE EXISTING |
| | FOOTING IS ADEQUATE TO SUPPORT THE BLOCK WALL? HOW DOES |
| | THE PROPOSED NEW WALL TIE INTO THE EXISTING STRUCTURE? |
| | HOW WILL THE PROPOSED NEW BLOCK WALL RESIST WIND AND |
| | OTHER LOADS FBC R301? |
| | |
| | 8. ONE SHEET SHOWS A GARAGE DOOR WITH A DRIVEWAY. IT IS |
| | NOT CLEAR IF THIS IS A PLAN OR AN ELEVATION. IS THE |
| | GARAGE DOOR PROPOSED OR EXISTING? THE PURPOSE OF THIS |
| | PAGE IS NOT CLEAR. |
| | |
| | |
| | |
| | |