| Plan Review Notes For Permit 09100194 |
| Permit Number |
09100194 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-10-08 16:37:24 | REROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- CLEARLY INDICATE ON NOA 09-0224.01 SUBMITTED WHICH | | | SPECIFIC APPROVED ASSEMBLY IS GOING TO BE INSTALLED. IF | | | SELECTED ASSEMBLY HAS MORE THAN ONE BASE SHEET | | | FASTENING OPTION, THEN INDICATE WHICH OPTION IS GOING | | | TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES OF SEC. 1609 OF 2007 FBC WITH 2009 REVISIONS. | | | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | | REQUIRED BY GENERAL LIMITATION #7. SEE GENERAL | | | LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. | | | ***NOTES: A) DESIGN PROFESSIONAL DOING THE RAS 117 | | | CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDING | | | TO SEC. 1609.4.3 OF 2009 REVISIONS TO THE 2007 FBC THIS | | | BUILDING IS LOCATED ON EXPOSURE "C", NOT ""B". | | | | | | B) APPROVED ASSEMBLIES THAT ARE LIMITED BY GENERAL | | | LIMITATION #9 CAN'T BE USED IN THIS BUILDING BECAUSE | | | THE ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES OF SEC. | | | 1609 FBC 2007. | | | | | | 3- SEPARATE PERMITS ARE REQUIRED FOR ANY ROOF | | | EQUIPMENT. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|