| Plan Review Notes For Permit 09100081 |
| Permit Number |
09100081 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-10-14 07:37:56 | ****PROVISO**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS | | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | PROVIDE TO INSPECTOR AT FIRST INSPECTION | | | | | | SEE PAGE 10 OF 20 - INCORRECT WIND DESIGN CRITERIA - | | | BASED ON AERIAL PHOTOGRAPHS, MINIMUM DESIGN CRITERIA IS | | | 140MPH EXPOSURE C | | | | | | THE ONLY SHEET SIGNED AND SEALED BY THE ENGINEER DOES | | | NOT INCLUDE ANY STRUCTURAL INFORMATION, SEE PAGE 6 OF | | | 20. PLEASE REVISE TO INCLUDE STRUCTURAL DETAIL. | | | | | | AT CONTRACTOR'S RISK | | | | | | |
|