| 2009-10-21 16:25:06 | STANDBY GENERATOR AND ABOVEGROUND STORAGE TANK (AST) |
| | |
| | 1. PLEASE PROVIDE PRODUCT APPROVALS FOR THE "FIREGUARD" |
| | INSULATED TANK (2085) AS DESCRIBED ON THE PLANS. SOME |
| | INFORMATION IS SHOWN ON PAGE A-04. |
| | |
| | 2. PLEASE ILLUSTRATE THE LOCATION OF ANY OPENINGS NEAR |
| | THE GENERATOR EXHAUST PIPE. |
| | |
| | 3. PLEASE PROVIDE PRODUCT APPROVALS FOR THE GENERATOR. |
| | |
| | 4. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE |
| | NATIONAL ELECTRICAL CODE. |
| | |
| | 5. ENTIRE INSTALLATION TO COMPLY WITH NFPA 30. |
| | |
| | 6. THE GENERATOR INSTALLATION SHALL ALSO COMPLY WITH |
| | NFPA 37. |
| | |
| | 7. SEVERAL REQUIREMENTS OF THE FLORIDA BUILDING CODE |
| | ARE NOT BEING MET WITH THE PROPOSED INSTALLATION. |
| | PLEASE SEE BUILDING REVIEWER NOTES. |
| | |
| | 8. AN ELEVATION DRAWING IS NEEDED WHERE THE PROPOSED |
| | EQUIPMENT IS BEING SHOWN. |
| | |
| | 9. BASED ON THE SIZE CAPACITY OF THE PROPOSED FUEL TANK |
| | A SEPARATE FIRE RATED ENCLOSURE APPEARS TO BE |
| | NECESSARY. |
| | |
| | 10. PLEASE ILLUSTRATE ON THE PLANS THE LOCATION OF THE |
| | TWO HOUR WALLS THAT SEPARATE THE PARKING STRUCTURE FROM |
| | OTHER PORTIONS OF THE BUILDING. |
| | |
| | |
| | DENIED |
| | |
| | |