Plan Review Notes
Plan Review Notes For Permit 09100020
Permit Number 09100020
Review Stop E
Sequence Number 1
Notes
Date Text
2009-10-10 09:11:09 
  
 ** DENIED **
  
 ** SOME OF THE COMMENTS BELOW WOULD TYPICALLY BE
 REDLINED HOWEVER NOT ALL. AS STATED IN ALL REVIEWS IF
 THERE ARE QUESTIONS ON ANY OF THE BELOW COMMENTS PLEASE
 DO NOT HESITATE IN CONTACTING THIS REVIEWER.
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE
 REFLECTED ON ELECTRICAL PLANS.
 2008 NFPA-70 (NEC)
 2002 NFPA-72
  
 *** THIS IS UNDER THE 2008 NEC WHICH HAS SEVERAL
 CHANGES WHICH WILL AFFECT THIS PROJECT.
  
 2) NOTE: PLEASE INCLUDE AIC RATING OF MAIN/SERVICE
 EQUIPMENT. 110.9
  
 3) NOTE: PANEL SCHEDULE NEEDS TO INCLUDE ALL BRANCH
 CIRCUIT SIZES SHOWING MINIMUM REQUIRED OVER CURRENT
 PROTECTION AND CONDUCTORS.
 PLEASE SEE 408.4,240.4,310.16, 210, 210.52 ETC
  
 4) NOTE: PLEASE BE SURE TO SEE 424.3B FOR MINIMUM
 SIZING FOR AHU/CU. PLEASE INCLUDE AHU ON ELECTRICAL
 LAYOUT.
  
 5) NOTE: CLOSET LIGHTS DO NOT MEET 410.8. SEE ASSUMED
 MINIMUM SHELVING PER SECTION GIVEN.
  
 6) NOTE: PLEASE SEE 210.52 FOR MISSING WALL RECEPTACLE
 IN FRONT CORNER BEDROOM. AS EACH ROOM IS NOT IDENTIFIED
 SEPARATELY SPECIFIC ROOMS ARE HARD TO STATE.
 PLEASE SEE 408.4 FOR THE 2008 NEC WHICH REQUIRES ALL
 SPACES/ROOMS AND AREAS TO BE SPECIFIC ON PANEL
 SCHEDULES. THIS ORIGINAL WAS REVISED IN THE 2005 NEC.
  
 7) NOTE: PLEASE LIST ALL ARC FAULT PROTECTED CIRCUITS
 PER 210.12. PLEASE SEE 2008 NEC
  
 8) NOTE: PLEASE SEE 406.8 FOR WEATHER RESISTANT
 RECEPTACLES
  
 9) NOTE: PLEASE SEE 406.11 FOR TAMPER RESISTANT
 RECEPTACLES.
  
 10) NOTE: RISER INDICATES A MAIN OUTSIDE HOWEVER THE
 PLANS ONLY INDICATE A METER. PLEASE SHOW.
 110.26
  
 11) NOTE: WASHER IS SHOWN IN FRONT OF DOOR AND WATER
 HEATER, IS THIS CORRECT?
  
 12) NOTE: PLEASE SEE WALL SPACE AT FRONT ENTRANCE WALL
 WHICH IS OVER 12FT AND NEEDS AN ADDITIONAL RECEPTACLE
 PER 210.52.
 SEE WALL SPACE BETWEEN STOVE AND REFRIGERATOR.
  
 13) NOTE: PLEASE SEE 422.13 AS THE WATER HEATER LOAD IS
 REQUIRED TO BE FIGURED AT 125%.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  