| 2009-11-12 11:10:00 | RESIDENTIAL (R3) RENOVATION, BUILDING REVIEW CHECKLIST. | | | 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- SCOPE OF WORK SHOWN ON THE PERMIT APPLICATION | | | DOESN'T MATCH SCOPE OF WORK SHOWN ON THE PLANS | | | SUBMITTED. REVISE AS REQUIRED. | | | | | | 2- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW. | | | SEC. 108.3 CITY AMENDMENTS TO FBC. NEED TO UPDATE VALUE | | | THAT REFLECTS ALL SCOPE OF WORK INCLUDING ALL PLUMBING, | | | ROOFING, BUILDING AND ELECTRICAL WORK SHOWN ON PLANS. | | | PERMIT FEES WILL BE ADJUST ACCORDINGLY. | | | | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9B-72 FOR: | | | A) STORM SHUTTERS TO BE INSTALLED. AND PROVIDE COMPLETE | | | INSTALLATION SCHEDULE. SEE ATTACHED SAMPLE. IN ADDITION | | | CLEARLY MARK ON STORM SHUTTERS DRAWINGS SPECIFIC | | | SHUTTERS MOUNTING CONDITIONS (EX: WALL MOUNTED, BUILT | | | OUT, ETC) AND SPECIFIC ANCHOR TYPE AND SPACING TO BE | | | USED ACCORDING TO THE OPENING DESIGN PRESSURES, | | | SHUTTERS PANEL SPAN, CONNECTION TYPE, EDGE DISTANCE AND | | | STRUCTURE TO BE ATTACHED TO (EX: WOOD FRAMED, CONCRETE | | | BLOCK, ETC). | | | | | | B) ROOF SHINGLES. | | | | | | 4- CLARIFY WHY THERE IS AN APPLICATION TO DEMOLISH | | | ENTIRE HOUSE. PERMIT #09070013. IS THIS HOUSE GOING TO | | | BE DEMOLISHED OR RENOVATED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|