| 2009-10-09 16:12:36 | PLANNING AND ZONING: **** FAILED **** |
| | |
| | 1. RESPOND TO COMMENTS IN WRITING. |
| | |
| | 2. SURVEY - THE SURVEY "PROPERTY ADDRESS" AND STREET |
| | NAME OF "SANDHILL WAY WEST" DOES NOT CORRELATE WITH THE |
| | PERMIT ADDRESS. THE SURVEY SHOWS 7500 SANDHILL WAY VS. |
| | 7108 EAGLE TERRACE. THE LEGAL DESCRIPTION, ADDRESS AND |
| | SURVEY DRAWING NEED TO MATCH. |
| | |
| | 3. THE LOCATION OF THE GENERATOR IS NOT TO SCALE, THE |
| | PROPOSED 14'-1" FROM THE PROPERTY LINE WILL PLACE THE |
| | GENERATOR CLOSER TO THE HOME AND ACCESSORY STRUCTURE. |
| | CLARIFY WHAT THE ACCESSORY STRUCTURE IS USED FOR? |
| | PROVIDE DRIVEWAY LOCATION ON SURVEY THAT IS WITHIN THE |
| | VICINITY OF THE ACCESSORY STRUCTURE. ALSO, PROVIDE THE |
| | GENERATOR'S ACTUAL DIMENSIONS ON THE SURVEY TO SCALE. |
| | PROVIDE A FLOOR PLAN OF THE TWO (2) BUILDINGS TO SHOW |
| | WHAT THE DISTANCE OF ANY OPENINGS ARE, SUCH AS |
| | WINDOWS/DOORS, IN RELATION TO THE GENERATOR. SHOW ALL |
| | INFORMATION ON ONE ENLARGED PLAN/SURVEY. |
| | |
| | 4. THE MINIMUM REQUIRED SIDE SETBACKS FOR A |
| | SINGLE-FAMILY WITHIN THE EAGLE'S ISLE IS 7.5'. INDICATE |
| | SETBACK DIMENSIONS FROM PROPOSED GENERATOR TO ALL |
| | PROPERTY LINES. PURSUANT TO SECTION 94-305(B)(4) OF THE |
| | ZONING AND LAND DEVELOPMENT REGULATIONS ("ZLDR"): |
| | MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET |
| | INTO A REQUIRED SETBACK. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. |
| | |