Plan Review Notes
Plan Review Notes For Permit 09100016
Permit Number 09100016
Review Stop E
Sequence Number 1
Notes
Date Text
2009-10-19 13:41:28 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} LOADS MUST NOT EXCEED GENERATOR OUTPUT. SUBMIT A
 LOAD CALCULATION FOR THE LOADS TO BE SERVED. IDENTIFY
 LOADS TO BE SERVED, PROVIDE A PANEL SCHEDULE FOR
 GENERATOR PANEL.
  
 2} THE PAD SUBMITTED WAS BOT DRAWN BY THE CONTRACTOR OF
 RECORD THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN
 MUST PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3.
 FBC. IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND
 471 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  