Plan Review Notes
Plan Review Notes For Permit 09100016
Permit Number 09100016
Review Stop B
Sequence Number 1
Notes
Date Text
2009-10-20 12:56:542007 FBC W/2009 REVISIONS
 RESIDENTIAL GENERATOR
  
 DENIED BY BUILDING
  
 1) SPECIFY HOW THE GENERATOR WILL BE ANCHORED TO THE
 CONCRETE PAD TO RESIST THE 140 MPH WIND SPEED. SPECIFY
 THE LOCATIONS, SIZE AND TYPE OF ANCHORS THAT WILL BE
 USED. FBC R301.1
  