2009-11-10 13:55:35DIESEL FUEL TANK TANK REPLACEMENT
  
 1. PLANS DO NOT INDICATE IF THE NEW DIESEL TANK
 COMPLIES WITH UL 142 OR UL 2085. PLEASE PROVIDE THIS
 INFORMATION ON THE PLANS.
  
 2. PLANS DO NOT INDICATE THAT THE NEW DIESEL TANK
 INSTALLATION AND APPURTENANT EQUIPMENT WILL BE
 INSTALLED IN ACCORDANCE WITH NFPA 30, THE FLAMMABLE AND
 COMBUSTIBLE LIQUIDS CODE.
  
 3. PLEASE PROVIDE PRODUCT APPROVALS FOR THE "FIREGUARD"
 TANK DESCRIBED ON THE PLANS.
  
 4. NO INFORMATION PROVIDED REGARDING PRODUCT LABELS,
 SAFETY LABELS OR WARNING LABELS OR NO SMOKING
 INFORMATION.
  
 5. PLEASE INDICATE ANY SAFETY EQUIPMENT PROVIDED NEAR
 THE PROPOSED DIESEL CONTAINMENT AREA. THIS SAFETY
 EQUIPMENT COULD INCLUDE FIRE HYDRANTS, WATER HOSES, OR
 PORTABLE FIRE EXTINGUISHERS.
  
 6. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR HANDRAIL SHOWN ON STAIR DETAIL.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  