| Plan Review Notes For Permit 09100005 |
| Permit Number |
09100005 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-11-10 13:55:35 | DIESEL FUEL TANK TANK REPLACEMENT | | | | | | 1. PLANS DO NOT INDICATE IF THE NEW DIESEL TANK | | | COMPLIES WITH UL 142 OR UL 2085. PLEASE PROVIDE THIS | | | INFORMATION ON THE PLANS. | | | | | | 2. PLANS DO NOT INDICATE THAT THE NEW DIESEL TANK | | | INSTALLATION AND APPURTENANT EQUIPMENT WILL BE | | | INSTALLED IN ACCORDANCE WITH NFPA 30, THE FLAMMABLE AND | | | COMBUSTIBLE LIQUIDS CODE. | | | | | | 3. PLEASE PROVIDE PRODUCT APPROVALS FOR THE "FIREGUARD" | | | TANK DESCRIBED ON THE PLANS. | | | | | | 4. NO INFORMATION PROVIDED REGARDING PRODUCT LABELS, | | | SAFETY LABELS OR WARNING LABELS OR NO SMOKING | | | INFORMATION. | | | | | | 5. PLEASE INDICATE ANY SAFETY EQUIPMENT PROVIDED NEAR | | | THE PROPOSED DIESEL CONTAINMENT AREA. THIS SAFETY | | | EQUIPMENT COULD INCLUDE FIRE HYDRANTS, WATER HOSES, OR | | | PORTABLE FIRE EXTINGUISHERS. | | | | | | 6. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS | | | FOR HANDRAIL SHOWN ON STAIR DETAIL. | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | |
|