| 2009-10-07 15:51:37 | ** DENIED ** |
| | |
| | 1) NOTE: TENANT SEPARATION REQUIRED BEFORE ADDITIONAL |
| | METERED SERVICE CAN BE GRANTED. |
| | FBC CHAPTER 3 FOR OCCUPANCY CLASSIFICATION. |
| | 230.2, 230.2E IDENTIFICATION FOR NEW MAINS. |
| | |
| | 2) NOTE: THE BUILDING IS NOW BEING PROPOSED AS A TOTAL |
| | 800AMP SERVICE WITH SERVICE ENTRANCE CONDUCTORS WHICH |
| | ARE ONLY RATED FOR 400AMPS. THERE IS NO OVER CURRENT |
| | PROTECTION WHICH WILL LIMIT THE LOAD ON CONDUCTORS |
| | ABOVE THE 400AMP RATING. |
| | ALONG WITH NOTE #1, THE LOAD DOES NOT INCLUDE |
| | INFORMATION FOR 400AMP SERVICE. |
| | PLEASE SEE 240.3 FOR PROTECTION OF CONDUCTORS. |
| | |
| | THIS HAS BEEN TAKEN TO CODE PANELIST FOR DETERMINATION |
| | BASED ON OTHER SECTIONS OF THE CODE. AS THERE IS NO |
| | OVER CURRENT PROTECTION FOR CONDUCTORS PLEASE ADJUST |
| | SERVICE SIZE OR CONDUCTORS. |
| | |
| | |
| | 3) NOTE: SEPARATE BUILDING PERMIT BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK FOR TENANT SEPARATION |
| | WILL BE REQUIRED. |
| | |
| | |
| | ** AS THERE IS INFORMATION NOT YET SUBMITTED REQUIRED |
| | FOR MINIMUM CODE COMPLIANCE REVIEW THERE MAY VERY WELL |
| | BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT |
| | BE MADE AT THIS TIME. |
| | |
| | |
| | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |