| 2009-10-02 08:23:12 | **PROVISO ** |
| | |
| | ** PLEASE REVISE AND SUBMIT THE INFORMATION BEFORE |
| | ROUGH. THIS WILL BE A REVISION. |
| | |
| | 1) NOTE: PLEASE SEE 13-415.AB.5, 13-415.B.1, LIGHT |
| | FIXTURE AND WATTAGE INFORMATION FOR BATHROOM IS NOT |
| | PERMITTED TO EXCEED TABLE ALLOWANCES. PLEASE PROVIDE |
| | FIXTURE INFORMATION AS PLANS ONLY STATE 2X2 FIXTURE? |
| | |
| | 2) NOTE: EMERGENCY LIGHTS ARE SHOWN CIRCUITED TO OTHER |
| | THAN THE LOCAL LIGHTING BRANCH CIRCUIT. PLEASE SEE |
| | 700.12F AS THE CODE REQUIRES EMERGENCY AND EXIT LIGHTS |
| | CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT. |
| | |
| | 3) NOTE: PLANS CONTAIN A NOTE WHICH MENTIONS NEW |
| | LIGHTING WIRING TO BE #14, HOWEVER THIS WOULD DEPEND ON |
| | THE EXISTING BRANCH CIRCUIT IN WHICH LIGHTS WILL BE |
| | CONNECTED. |
| | 310.16,240.4 ETC VIF |
| | |
| | 4) NOTE: PLEASE SEE FBC 13-415.AB.1.1,.1.2. THE NEW |
| | LIGHTING CONTROLS FOR EACH NEW ROOM MUST MEET |
| | PRESCRIPTIVE REQUIREMENTS FOR SOME SORT OF AUTOMATED |
| | LIGHTING CONTROLS. THIS REQUIRES ONLY NEW BEING |
| | INSTALLED NOT OTHER AREAS OF THE OFFICE/TENANT SPACE. |
| | |
| | ** PLEASE BE AWARE THAT TWIST TYPE TIMERS ARE NOT |
| | PERMITTED PER FBC CHAPTER 11. 11-4.27.4 |
| | |
| | |
| | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |