| Plan Review Notes For Permit 09090649 |
| Permit Number |
09090649 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-12-15 13:16:25 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- PROVIDE INFORMATION SHOWING COMPLIANCE WITH THE ROOF | | | VENTILATION AS REQUIRED BY SEC. R806.1 OF 2007 FLORIDA | | | RESIDENTIAL CODE. REVISE CALCULATIONS SHOWN ON SHEET | | | A1. NEED TO INCLUDE THE OVERALL ROOF AREA NOT JUST THE | | | A/C AREA. ALSO, SIZE OF GABLE VENTS TO PROVIDE THE | | | REQUIRED VENTILATION. PROVIDE CALCULATIONS SHOWING THE | | | ACTUAL CLEAR AREA OF THE SPECIFIED VENTS. | | | |
|