| 2009-10-10 07:48:55 | |
| | |
| | ** DENIED ** |
| | |
| | ** SOME OF THE COMMENTS BELOW WOULD TYPICALLY BE |
| | REDLINED HOWEVER NOT ALL. AS STATED IN ALL REVIEWS IF |
| | THERE ARE QUESTIONS ON ANY OF THE BELOW COMMENTS PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS REVIEWER. |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE |
| | REFLECTED ON ELECTRICAL PLANS. |
| | 2005 NFPA-70 (NEC) |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE INCLUDE AIC RATING OF MAIN/SERVICE |
| | EQUIPMENT. 110.9 |
| | |
| | 3) NOTE: PLEASE SEE 250.6, 250.24 AS AN EQUIPMENT |
| | GROUNDING CONDUCTOR IS SHOWN BEFORE THE FIRST MEANS OF |
| | DISCONNECT WHICH IS NOT PERMITTED. AS THE |
| | GROUNDED/NEUTRAL CONDUCTOR IS BONDED AT THE FIRST MEANS |
| | OF DISCONNECT THIS WOULD PARALLEL THE NEUTRAL CREATING |
| | OBJECTIONABLE CURRENTS. |
| | |
| | 4) NOTE: PLEASE SEE MASTER BATH. GFI RECEPTACLE SPACE |
| | MUST MEET 210.52D. THE LOCATION OF THE GFI IS REQUIRED |
| | TO BE WITHIN 3FT OF SINK EDGE WITHOUT CROSSING OVER |
| | ANOTHER SINK. PLEASE RELOCATE GFI OR ADD AND ADDITIONAL |
| | RECEPTACLE. |
| | |
| | 5) NOTE: PANEL SCHEDULE DOES NOT LIST THE REQUIRED |
| | DEDICATED CIRCUITING FOR BATH(S) PER 210.11C3. IT IS |
| | PERMISSIBLE TO WIRE TWO DIFFERENT WAY HOWEVER IN ANY |
| | CASE THE MINIMUM CIRCUIT REQUIRED IS REQUIRED TO BE |
| | 20AMP AND #12 AWG. |
| | |
| | 6) NOTE: THE MECHANICAL PLANS INDICATE THE HEAT STRIP |
| | KW AT 10KW WHICH ON A HOUSE OF THIS SIZE IS ABOUT |
| | RIGHT. HOWEVER THE ELECTRICAL PANEL SCHEDULE STATES |
| | 5KW. |
| | PLEASE COORDINATE AND ADJUST OVER CURRENT PROTECTION |
| | AND BRANCH CIRCUIT SIZING PER 240.4,310.16 AND MINIMUM |
| | 125% PER 424.3B |
| | |
| | 7) NOTE: ALONG WITH COMMENT #6 ABOVE, IF THE HEAT LOAD |
| | IS LARGE THAN THE COOLING LOAD THEN THE HEAT LOAD WOULD |
| | THEN BE FIGURED INTO THE LOAD CALCULATIONS. 220.60 |
| | |
| | 8) NOTE: PLANS INDICATES THE SERVICE AS EXISTING |
| | HOWEVER HOW IS THIS POSSIBLE WHEN THIS IS A NEW SFR? |
| | PLEASE INCLUDE THE SERVICE ENTRANCE CONDUCTORS PER |
| | 310.15B6 OR 310.16. |
| | |
| | 9) NOTE: PLEASE KITCHEN COUNTER SPACE TO THE RIGHT OF |
| | THE SINK LOCATION WHICH WILL REQUIRE AND ADDITIONAL GFI |
| | PER 210.52C1-5. 210.8A6 FOR GFI PROTECTION. |
| | |
| | 10) NOTE: A CHANGE IN THE 2005 NEC WAS 210.8A7 WHICH |
| | REQUIRED ALL RECEPTACLES LOCATED WITHIN 6FT OF LAUNDRY |
| | SINKS TO BE GFI/GFI PROTECTED. THIS INCLUDES ANY |
| | DEDICATED CIRCUITS/RECEPTACLES SUCH AS WASHING |
| | MACHINES. |
| | |
| | 11) NOTE: PLEASE SEE 408.4 AS ANOTHER CHANGE IN THE |
| | 2005 NEC WAS THAT ALL PANEL SCHEDULES SHALL BE MORE |
| | SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. THE USE |
| | OF *GENERAL LIGHTING AND GENERAL RECEPTACLES* WAS NO |
| | LONGER ACCEPTABLE. THE RECORD SET OF PLANS WILL BE |
| | REQUIRED TO HAVE PANEL SCHEDULE UPDATED BEFORE FINAL. |
| | THIS ITEM COULD BE DONE AS A PROVISO. |
| | AT THAT TIME ALL ARC FAULT PROTECTED CIRCUITS ARE |
| | REQUIRED TO BE LISTED. PLANS ONLY CONTAIN A NOTE THAT |
| | MENTIONS ALL OUTLETS IN BEDROOMS TO BE PROTECTED. THIS |
| | PROJECT IS UNDER THE 2005 NEC AND NOT THE 2008. 210.12 |
| | |
| | 12) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.52 AS |
| | ONE OR MORE OF THE TWO MINIMUM SMALL APPLIANCE CIRCUITS |
| | TO BE SHOWN AND FIGURED AT 1500VA. PLEASE SEE 210.52B1 |
| | AS DINING ROOMS, BREAKFAST AREAS AND AREAS OF THE LIKE |
| | ARE ALL CONSIDERED UNDER THE SMALL APPLIANCE RULES OF |
| | THE CODE. IF THERE IS AN ADDITIONAL DINING ROOM |
| | RECEPTACLE CIRCUIT OR FLORIDA/BREAKFAST ROOM RECEPTACLE |
| | CIRCUIT THEN EACH ONE ABOVE THE TWO MINIMUM SMALL |
| | APPLIANCES WOULD BE REQUIRED TO BE AN ADDITIONAL |
| | 1500VA. |
| | PLEASE ADJUST AS NEEDED. AS THE PANEL SCHEDULE IS NOT |
| | SPECIFIC IT IS NOT POSSIBLE TO GIVE A ACCURATE REVIEW |
| | OF THE LOADS AND CIRCUITING FOR MINIMUMS. |
| | |
| | 13) NOTE: THE LIVING ROOM NORTHEAST WALL IS OVER 12FT |
| | WHICH WOULD REQUIRE AT LEAST ONE ADDITIONAL RECEPTACLE |
| | PER 210.52. |
| | |
| | 14) NOTE: PLANS INDICATE SMOKE DETECTORS. PLEASE SEE |
| | NFPA-72 AS SMOKE DETECTORS ARE ONLY DEVICES WHICH |
| | DETECT AND DO NOT SOUND AN ALARM. WILL THERE BE A FIRE |
| | ALARM PANEL AND SOUNDING DEVICES? |
| | SMOKE ALARMS ARE DEVICES THAT DETECT AND SOUND AN |
| | ALARM. SHOULD THESE BE SA AND SMOKE ALARMS? |
| | PLEASE SEE 11.5.1,11.8.3 OF NFPA AND CHAPTER 9 OF FBC |
| | FOR DEFINTIONS. |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |