| 2009-10-22 16:39:11 | DENIED |
| | REFERENCE: |
| | FBC-2007 EXISTING BUILDING |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 11 |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. SHT A-2 DETAIL #2. BATHROOM 202 PER SECTION 906.1 |
| | SHALL BE ACCESSIBLE. ACCESSIBILITY IN PORTIONS OF |
| | BUILDINGS UNDER-GOING A CHANGE OF OCCUPANCY |
| | CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE |
| | FLORIDA BUILDING CODE, BUILDING. (11-4.1.3(11)). |
| | ****RESPONSE NOTED, BUT SINCE THE OCCUPANCY OF THE |
| | ORIGINAL DESIGN FOR THE SPACE WAS R-2 AND THE OCCUPANCY |
| | IS BEING CHANGED TO BUSINESS THE FACT THAT THE BATHROOM |
| | IS EXISTING DOES NOT EXEMPT THE BATHROOM FROM MEETING |
| | THE CODE REQUIREMENTS. |
| | |
| | 2. SHT A-2 PER TABLE 403.1 A DRINKING FOUNTAIN IS |
| | REQUIRED. PLEASE SHOW THE LOCATION OF THE REQUIRED |
| | DRINKING FOUNTAIN. |
| | ****RESPONSE NOTED, BUT NO DRINKING FOUNTAIN IS |
| | INDICATED IN THE COMMON AREA. SUBMIT PLANS SHOWING THE |
| | LOCATION OF THE EXISTING DRINKING FOUNTAIN. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |