| Plan Review Notes For Permit 09090630 |
| Permit Number |
09090630 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-10-02 07:56:45 | **DENIED ** | | | | | | | | | | | | 1) NOTE: NO LIGHTING PERFORMANCE CALCULATIONS/LIGHTING | | | DENSITIES SUBMITTED. 13-415.AB.5, 13-415.B.1. | | | SOME FIXTURES ON PLANS NEED IDENTIFICATION TO | | | COORDINATE WITH CALCULATIONS AND FIXTURE LEGEND. ( SEE | | | STAIR LIGHTS) | | | | | | 2) NOTE: ELECTRICAL PANEL NOT PERMITTED IN STORAGE | | | CLOSET. 110.26,240.24D | | | | | | 3) NOTE: STORAGE TYPE WATER HEATERS SHALL BE FIGURED AT | | | 125% AS THESE ARE CONSIDERED CONTINUOUS LOADS. 422.13 | | | WOULD HAVE BEEN REDLINED IF THIS WAS THE ONLY COMMENT. | | | | | | 4) NOTE: PLEASE ADJUST AND COORDINATE SOME CIRCUITS. | | | SEE CIRCUITING ON PLANS FOR HPU AND WATER HEATER. WH | | | SHOWN ON CIRCUITS 1,3 AND HPU ON 22,24. THIS SHOULD BE | | | REVERED. | | | ALSO WOULD HAVE BEEN REDLINED IF NOT FOR COMMENTS #1 | | | AND #2. | | | | | | ** PLANS ARE ALSO COMING BACK FOR BUILDING REVIEW | | | COMMENTS. | | | | | | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|