| Plan Review Notes For Permit 09090612 |
| Permit Number |
09090612 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-01-05 11:10:51 | ** DENIED * | | | | | | 1) NOTE: PREVIOUS REVIEW NOTES MENTIONED THE REQUIRED | | | 8HR BACK UP TIME. THE RESPONSE MENTIONED 6 PLUS HRS | | | HOWEVER NOT MEETING THE MINIMUM TIMES PER CFR TITLE 24 | | | 12.2. | | | PLEASE CLARIFY WHERE THE ADDITION BACK UP WILL BE | | | PROVIDED. WILL THIS BE BY ADDITIONAL BATTERY BACK UP? | | | | | | 2) NOTE: THE APPLIED VALUE FOR COMPLETED SCOPE OF WORK | | | IS TO INCLUDE THE FOLLOWING PER FBC 108.3 AS ADOPTED BY | | | THE CITY OF WEST PALM BEACH. | | | DESIGN COST, ALL LABOR, MATERIALS, EQUIPMENT ETC EVEN | | | IF ANY OF THESE ITEMS ARE OWNER SUPPLIED. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | |
|