| 2009-10-06 16:22:00 | DENIED |
| | REFERENCE: |
| | FBC-2007 FUEL GAS |
| | |
| | A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS |
| | PERMIT: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR |
| | 2007 FUEL GAS CODE. - THE ISOMETRIC SUBMITTED INDICATES |
| | THAT THE METER IS LOCATED ON THE ROOF. THE METER SHALL |
| | BE LOCATED ON THE GROUND LEVEL OUTSIDE THE BUILDING. - |
| | PER CONVERSATION WITH FLORIDA PUBLIC UTILITIES, THE |
| | METER SHALL NOT BE ON THE ROOF. |
| | |
| | 2. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2007 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). -- INDICATE DISTANCE FROM |
| | METER ON THE GROUND LEVEL. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |