| Plan Review Notes For Permit 09090612 |
| Permit Number |
09090612 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-10-21 14:44:33 | ** DENIED ** | | | | | | | | | | | | 1) NOTE: PLEASE SUBMIT MANUFACTURE SPECS/CUT SHEETS FOR | | | ALL PROPOSED *WIRELESS* SYSTEMS PROPOSED ON PLANS. | | | PLEASE SEE 230.76,230.79,225.39 AS ALL DEVICES SHALL BE | | | RATED FOR THE LOAD SERVED FOR DISCONNECTING MEANS OF | | | SERVICE ENTRANCE OR FEEDERS. | | | IT IS UNCLEAR WHY MOST OF THE EQUIPMENT ON PLANS IS | | | LABELED AS *WIRELESS*. | | | 110.3,90.7 | | | | | | 2) NOTE: PLEASE PROVIDE NOTES FOR SIGNAGE REQUIRED PER | | | 230.2E, 702.8 | | | | | | 3) NOTE: PLANS INDICATED *EXISTING BATTERY CABINETS*. | | | PLEASE INDICATE TIME FOR BACK UP OF EXISTING SYSTEMS. | | | | | | 4) NOTE: PLEASE INDICATE VERTICAL SUPPORT OF CONDUCTORS | | | PER 300.19 | | | | | | 5) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES | | | ARE ON PLANS. | | | 2005 NFPA-70 | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|