| 2009-10-27 19:36:13 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PLAN INDICATES THAT VENTILATION AND COMBUSTION AIR | | | FOR THE GENERATOR IS TO BE TRANSFERRED THROUGH A | | | LOADING DOCK INTO THE GENERATOR ROOM. THIS | | | CONFIGURATION IS NOT PERMITTED. VENTILATION AIR SHALL | | | BE SUPPLIED DIRECTLY FROM A SOURCE OUTSIDE OF THE | | | BUILDING BY AN EXTERIOR WALL OPENING OR FROM A SOURCE | | | OUTSIDE THE BUILDING BY A 2-HOUR FIRE RATED AIR | | | TRANSFER SYSTEM IN ACCORDANCE WITH NFPA 110-02 SECTION | | | 7.7.3. | | | | | | 2. THE VENTILATION SUPPLY IS SHOWN BEING BROUGH INTO | | | THE GENERATOR ROOM THROUGH A NEW 6' X 4' WALL OPENING | | | IN THE BUILDING. WITH THIS OPENING, HOW WILL THE | | | REQUIRED FIRE RATING OF THE GENERATOR ROOM BE | | | MAINTAINED? THE ROOM SHALL HAVE A MINIMUM 2-HOUR FIRE | | | RATING IN ACCORDANCE WITH NFPA 110-02 SECTION 7.2.1.1. | | | ALSO, FIRE DAMPERS OR OTHER SELF-CLOSING DEVICES SHALL | | | NOT BE PERMITTED IN VENTILATION OPENINGS OR DUCTWORK | | | FOR SUPPLY OR RETURN/DISCHARGE AIR TO EPS EQUIPMENT FOR | | | LEVEL 1 EPSS IN ACCORDANCE WITH NFPA 110-02 SECTION | | | 7.7.2.3. SHOW HOW THE FIRE RATING OF THE ROOM IS TO BE | | | MAINTAINED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|