| 2009-10-11 09:54:45 | |
| | |
| | ** DENIED ** |
| | |
| | |
| | 1) NOTE: PLANS SUBMITTED FOR PERMIT AFTER MARCH 1ST |
| | 2009 AND DECEMBER 31ST, 2008 ARE UNDER THE FOLLOWING |
| | CODES. THE LIFE SAFETY CODE ON PLANS STATE 2000 EDITION |
| | WHICH IS ACTUALLY FROM TWO CYCLES AGO. PLEASE SEE FAC |
| | 69A FOR ADOPTIONS OF NFPA EDITIONS. |
| | FAC 69A-60.004, 69A-3.012 AS OF DECEMBER 31ST 2008 |
| | ADOPTED THE 2006 NFPA-101, 2006 NFPA-1 AND THE 2007 |
| | FLORIDA FIRE PREVENTION CODE. |
| | PLEASE SEE FBC 2007 W/ 2009 SUPPLEMENTS, FAC 69A-3.012 |
| | AS DECEMBER 8TH, 2006 THE ELECTRICAL CODE IS THE 2005 |
| | EDITION. |
| | PLEASE ADJUST PLANS TO THE FOLLOWING WHICH ARE |
| | RELEVANT. |
| | |
| | 2007 FBC W/2009 REVISIONS. |
| | 2005 NFPA-70 |
| | 2005 NFPA-110 |
| | 2006 NFPA-101 |
| | |
| | ** FOR INFORMATION ONLY 2008 NFPA-70 WAS ADOPTED ON |
| | OCTOBER 1ST, 2009. |
| | |
| | 2) NOTE: SEE NFPA-110 7.7.2.1 AND 7.7.2.2. THE MAKE UP |
| | AIR IS SHOWN FROM AN INSIDE LOADING DOCK WHICH IS |
| | SUPPLIED THROUGH ANOTHER OPENING. PLANS ALSO INDICATE A |
| | *SCREEN GATE/DOOR OPENING* AT THE SAME LOCATION WHERE |
| | VENTILATION IS BEING BROUGHT INTO? |
| | SEE MINIMUM CODES AND RATING OF AIR INTAKES. |
| | THIS WILL BE PART OF MECHANICAL REVIEW FOR TECHNICAL |
| | REVIEW COMMENTS AND IS GIVEN AS INFORMATION ONLY BY |
| | THIS REVIEWER. THE REVIEW OF THE VENTILATION SYSTEM IS |
| | NOT UNDER THIS ELECTRICAL REVIEW. |
| | |
| | 3) NOTE: PLANS INDICATE WHAT WOULD BE A NEW EXIT AND |
| | STAIRS HOWEVER NO LIGHTING PLANS WERE SUBMITTED FOR |
| | GENERAL ILLUMINATION OR FOR EGRESS ILLUMINATION. |
| | PLEASE SEE FBC 1006.1, NFPA-101 7.8.1.3,7.9.1.1,7.9.2 |
| | AND INDICATE. |
| | |
| | 4) NOTE: PLEASE SEE NFPA-110 7.3 FOR MINIMUM LIGHTING |
| | REQUIRED IN NEW GENERATOR ROOM. |
| | |
| | 5) NOTE: PLANS MAKE NOTE TO 700.27 FOR SELECTIVE |
| | COORDINATION HOWEVER NO COORDINATION STUDY AND |
| | DOCUMENTS WERE SUBMITTED. IF THIS INFORMATION IS NOT |
| | KNOWN BASED ON EQUIPMENT, BREAKERS ETC THIS CAN BE DONE |
| | AS A PROVISO TO BE SUBMITTED AT A LATER DATE. |
| | |
| | 6) NOTE: PLEASE EXPLAIN WHAT TYPE OF GENERATOR IS BEING |
| | REPLACED AND LOADS SERVED? THE PLANS ALL LEND TO A 700, |
| | 701 SYSTEM HOWEVER BASED ON PANEL SCHEDULES THERE ARE |
| | 700, 701 AND 702 ALL WIRED INTO THE SAME PANELS ALL FED |
| | FROM THE SAME TRANSFER SWITCH. THIS IS NOT PERMITTED. |
| | A/C EQUIPMENT, GENERAL PURPOSE RECEPTACLES, GENERAL |
| | LIGHTING ETC ARE NOT 700 SYSTEMS AND MAY NOT BE WIRED |
| | INTO LIFE SAFETY/EMERGENCY SYSTEMS. |
| | PLEASE PROVIDE PLANS FOR LIFE SAFETY LIGHTING |
| | CIRCUITS/LAYOUTS. IF ALL MINIMUM LIFE SAFETY REQUIRED |
| | EGRESS LIGHTING IS BATTERY BACK UP THEN ALL LIGHTING |
| | WOULD BE CONSIDERED AS AN 702 BACK UP AND NOT BE FED |
| | FROM THE 700 ATS. |
| | SEE NEC 700.9B, SEE HANDBOOK AS THERE ARE FIGURES WHICH |
| | CLEARLY SHOW SYSTEM SEPARATIONS. |
| | RISER INDICATES A 225AMP BREAKER TO RE-FEED EM-CONTROL |
| | PANEL HOWEVER NO INFORMATION FOR WHAT THIS PANEL IS |
| | FEEDING IS SHOWN. NO TRANSFER SWITCH IS SHOWN. WILL |
| | THIS PANEL BE FED FROM THE GENERATOR ONLY WHEN UNDER |
| | EMERGENCY POWER? |
| | PLANS ALSO STATE EXISTING WIRING AND LOADS HAVE NOT |
| | BEEN VERIFIED. SOME CODE REVIEW ITEMS CAN NOT BE |
| | CONFIRMED IF PLANS STATE THESE MAY NOT BE THE LOADS AND |
| | WIRING? |
| | |
| | 7) NOTE: PLEASE INDICATE THE GROUNDING FOR T-EM? |
| | 250.20,250.30,250.66 ETC |
| | |
| | 8) NOTE: PLEASE SEE NFPA- 110 7.4, 7.5 FOR LOCATIONS, |
| | ATTACHMENTS ETC. |
| | |
| | |
| | ** AS THERE WILL BE SEVERAL CHANGES MADE TO RISER, |
| | PLEASE CALL TO GO OVER ANY ITEMS BEFORE RESUBMITTING TO |
| | ALLEVIATE DELAY OF PROJECT. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |