| Date |
Text |
| 2009-10-06 15:42:49 | BUILDING PLAN REVIEW |
| | PERMIT: 09090605 |
| | ADD: 111 SAPODILLA AV |
| | CONT: KNIGHT ELECTRIC COMANPY |
| | TEL: (561)689-3500 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | OCT 6/ 2009 |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH 2009 SUPPLEMENTS. |
| | |
| | PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING |
| | BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO |
| | WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS |
| | PERMIT. |
| | 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 403, 404 AND 405 OF THIS CODE. |
| | SHEET A0.1 INDICATES A LEVEL 1 ALTERATION. PLEASE |
| | REVIEW EXIST BLDG CODE SECTION SECTION 404 |
| | ALTERATION???LEVEL 2 - |
| | 404.1 SCOPE. LEVEL 2 ALTERATIONS INCLUDE THE |
| | RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION |
| | OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION |
| | OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL |
| | EQUIPMENT. |
| | |
| | 2) MISSING WIND DESIGN INFORMATION:1603.1.4 WIND DESIGN |
| | DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM |
| | OF THE BUILDING: |
| | 2.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| | (KM/HR). |
| | |
| | 2.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| | |
| | 2.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| | DIRECTION SHALL BE INDICATED. |
| | |
| | 2.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 2.5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| | IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION |
| | OF EXTERIOR COMPONENTS AND CLADDING |
| | MATERIALS NOT SPECIFICALLY DESIGNED BY THE REGISTERED |
| | DESIGN PROFESSIONAL. |
| | |
| | 3) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING |
| | REPORTS ARE AS FOLLOWS: |
| | 3.1 WALL LOUVER |
| | |
| | 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 5) SHEET A1.1 PLEASE REVIEW NEW STAIR BOTTOM LANDING |
| | AND SWING OF NEW DOORWAY AND SECTION 1009.4 EXCEPTION# |
| | 2. DOORS OPENING ONTO A LANDING SHALL NOT REDUCE THE |
| | LANDING TO LESS THAN ONE-HALF THE REQUIRED WIDTH. WHEN |
| | FULLY OPEN, THE DOOR SHALL NOT PROJECT MORE THAN 7 |
| | INCHES (178 MM) INTO A LANDING. |
| | PLEASE PROVIDE DIMENSIONS. |
| | |
| | 6) SHEET A1.1 FOOTNOTE "G"INDICATES A NEW GAURDRAIL BUT |
| | IT THE PLANS MAKE IT APPEAR THERE IS A WALL STILL IN |
| | THAT LOCATION. PLEASE PROVIDE OPENING LIMITATIONS. |
| | 1013.3, 1607.7.1.1 CONCENTRATED LOAD. HANDRAIL |
| | ASSEMBLIES AND GUARDS SHALL BE ABLE TO RESIST A SINGLE |
| | CONCENTRATED LOAD OF 200 POUNDS (0.89 KN), APPLIED IN |
| | ANY DIRECTION AT ANY POINT ALONG THE TOP, AND HAVE |
| | ATTACHMENT DEVICES AND SUPPORTING STRUCTURE TO TRANSFER |
| | THIS LOADING TO APPROPRIATE STRUCTURAL ELEMENTS OF THE |
| | BUILDING. |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |