| Plan Review Notes For Permit 09090592 |
| Permit Number |
09090592 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-10-11 11:05:20 | | | | ** DENIED/TEMPORARY | | | | | | 1) NOTE: THE APPLICATION ADDRESS AS APPLIED ON PERMIT | | | APPLICATION IS STATING 905 45TH ST. THIS IS NOT THE | | | SAME AS LOCATION IN OUR SYSTEM UNDER THIS PCN OR THE | | | PLANS. THE PLANS STATE 901. INFORMATION HAS BEEN SENT | | | TO ADDRESSING REVIEW TO DETERMINE ACTUAL LOCATION. IF | | | ADDRESS DOES CHANGE TO 905, THEN CONTRACTOR MAY ADJUST | | | PLANS WITHOUT REPRINTING ALL SHEETS. | | | SEE NOTE #2 BELOW. | | | | | | | | | 2) NOTE: THE SECOND SET OF ELECTRICAL PLANS ARE NOT | | | SIGNED, DATED OR SEALED BY THE ENGINEER OF RECORD. | | | PLEASE SEE FAC 61G15-23.002 WHICH REQUIRES ALL SETS OF | | | DOCUMENTS INCLUDING JOBSITE SET AND OWNER SETS TO BE | | | SIGNED, DATED AND SEALED ALSO. FS 471.025. | | | AS THE ENGINEER OF RECORD IS LOCAL, A TIME CAN BE SET | | | UP FOR ENGINEER TO COME INTO OFFICE TO SIGN AND SEAL | | | PLANS. IDENTIFICATION OF DESIGN PROFESSIONAL MAY BE | | | REQUIRED WHEN APPEARING IN PERSON. | | | THE OTHER OPTION WOULD BE FOR THREE NEW SHEETS TO BE | | | BROUGHT IN AND INSERTED INTO SETS BY THE CONTRACTOR. A | | | TIME WOULD NEED TO BE SET UP FOR THIS TO TAKE PLACE. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|