Plan Review Notes
Plan Review Notes For Permit 09090592
Permit Number 09090592
Review Stop E
Sequence Number 1
Notes
Date Text
2009-10-11 11:05:20 
 ** DENIED/TEMPORARY
  
 1) NOTE: THE APPLICATION ADDRESS AS APPLIED ON PERMIT
 APPLICATION IS STATING 905 45TH ST. THIS IS NOT THE
 SAME AS LOCATION IN OUR SYSTEM UNDER THIS PCN OR THE
 PLANS. THE PLANS STATE 901. INFORMATION HAS BEEN SENT
 TO ADDRESSING REVIEW TO DETERMINE ACTUAL LOCATION. IF
 ADDRESS DOES CHANGE TO 905, THEN CONTRACTOR MAY ADJUST
 PLANS WITHOUT REPRINTING ALL SHEETS.
 SEE NOTE #2 BELOW.
  
  
 2) NOTE: THE SECOND SET OF ELECTRICAL PLANS ARE NOT
 SIGNED, DATED OR SEALED BY THE ENGINEER OF RECORD.
 PLEASE SEE FAC 61G15-23.002 WHICH REQUIRES ALL SETS OF
 DOCUMENTS INCLUDING JOBSITE SET AND OWNER SETS TO BE
 SIGNED, DATED AND SEALED ALSO. FS 471.025.
 AS THE ENGINEER OF RECORD IS LOCAL, A TIME CAN BE SET
 UP FOR ENGINEER TO COME INTO OFFICE TO SIGN AND SEAL
 PLANS. IDENTIFICATION OF DESIGN PROFESSIONAL MAY BE
 REQUIRED WHEN APPEARING IN PERSON.
 THE OTHER OPTION WOULD BE FOR THREE NEW SHEETS TO BE
 BROUGHT IN AND INSERTED INTO SETS BY THE CONTRACTOR. A
 TIME WOULD NEED TO BE SET UP FOR THIS TO TAKE PLACE.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  