| 2009-09-28 13:13:26 | DENIED |
| | REFERENCE: |
| | FBC-2007 RESIDENTIAL |
| | |
| | A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE |
| | PLUMBING PERMIT: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR |
| | 2007 FUEL GAS CODE. |
| | |
| | 2. TYPE OF GAS, (LP OR NATURAL). INDICATE ON PLANS. |
| | |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2007 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU |
| | G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8). (TOTAL |
| | BTU LOAD NOT INDICATED). |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2007 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | 5. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2007 FUEL GAS CODE |
| | SECS. 502 THRU 505 & RESIDENTIAL CODE SECS. G2426 THRU |
| | G2429. (NO OPENINGS WERE INDICATED NEAR THE TANKLESS |
| | WATER HEATERS. VENT SHALL BE MINIMUM DISTANCE FROM |
| | OPENINGS AS REQUIRED BY MANUF. INSTALLATION |
| | INSTRUCTIONS). |
| | |
| | 6. THE MOST REMOTE OUTLET APPEARS TO BE AT LEAST 90 FT |
| | FROM THE METER. WITH A TOTAL LOAD OF 746,000 BTU |
| | MINIMUM 2 INCH PIPE IS REQUIRED FROM THE METER UP TO |
| | THE TEE FOR THE GRILL, WITH 1-1/2 INCH UP TO THE TEE |
| | FOR THE POOL HEATER, AND 1-1/4 INCH UP TO THE TEE FOR |
| | BETWEEN THETANKLESS WATER HEATERS WITH 1 INCH REQUIRED |
| | UP THRU THE SHUT OFF VALVES TO EACH TANKLESS WATER |
| | HEATER. TABLE G2413.4(1). -- THE P.E. PIPING TO THE |
| | POOL HEATER IS REQUIRED TO BE MINIMUM 1-1/4 INCH PER |
| | TABLE G2413.4(7) UP THRU THE SHUT OFF VALVE. |
| | |
| | B. THE PERSON RESPONSIBLE FOR THE DESIGN AND DRAWINGS |
| | SHALL PRINT THEIR NAME AND PLACE THEIR SIGNATURE ON THE |
| | PLANS SUBMITTED FOR PUBLIC RECORD. SECTIONS 106.1 & |
| | 106.3.4.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |