| Notes |
| Date |
Text |
| 2009-10-07 11:07:10 | **PROVISO** | | | REVISION REQUIRED: | | | | | | 1. CONDENSATE SHALL NOT DISCHARGE TO SANITARY SEWER PER | | | CITY ORDINANCE. DISCHARGE CONDENSATE TO AN APPROVED | | | LOCATION PER FBC-M 307.2.1. THE EXISTING BUILDING | | | CONTAINS A COMMON CONDENSATE DISPOSAL PIPING SYSTEM FOR | | | MOST, IF NOT ALL, TENANT SPACES WHICH MAY BE UTILIZED. | | | OTHERWISE, PLEASE CALL TO DISCUSS PRIOR TO REVISING | | | PLANS. | | | | | | 2. THE INCORRECT ADDRESS WAS PROVIDED IN TITLE BLOCK OF | | | PLANS. SHOW THE CORRECT ADDRESS ON PLANS TO CORRESPOND | | | WITH THE ADDRESS SHOWN ON THE PERMIT. | | | | | | NOTE: SEPARATE ELECTRICAL PERMIT REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|