| 2009-10-11 08:59:01 | |
| | |
| | ** DENIED ** |
| | |
| | |
| | 1) NOTE: PLANS SUBMITTED FOR PLAN REVIEW ONLY AND HAVE |
| | NOT BEEN SUBMITTED UNDER PERMIT APPLICATION BY A |
| | LICENSED CONTRACTOR. |
| | PLANS ALSO STATE FOR PLAN REVIEW ONLY. |
| | |
| | 2) NOTE: WHEN SUBMITTING FOR PERMIT. PLEASE BE AWARE OF |
| | RECENT CODE CHANGES SUCH AS THE ADOPTION OF THE 2008 |
| | NEC. |
| | PLANS WILL BE REQUIRED TO STATE THE RELEVANT CODES FOR |
| | WHICH DESIGN IS RELEVANT. |
| | IF SUBMITTING FOR PERMIT AFTER OCTOBER 1ST, 2009 THE |
| | FOLLOWING FOR ELECTRICAL REVIEW WOULD NEED TO BE ON |
| | PLANS. |
| | 2007 FBC W/2009 SUPPLEMENTS. |
| | 2008 NFPA-70 |
| | |
| | 3) NOTE: WHEN SUBMITTING FOR PERMIT PLEASE BE SURE |
| | PLANS ARE SIGNED, DATED AND SEALED BY THE RESPONSIBLE |
| | DESIGNER OF RECORD. |
| | FAC 61G15-23.002, FS 471.025 |
| | |
| | 4) NOTE: PLEASE EXPAND ON THE DISCONNECTING MEANS AT |
| | THE DETACHED BUILDINGS. PLANS CONTAIN A NOTE FOR A |
| | DISCONNECT HOWEVER NO OTHER INFORMATION. |
| | 225.31-225.39 |
| | |
| | 5) NOTE: PLEASE SEE 250.32, 250.32 D OF THE NEC FOR |
| | GROUNDING ELECTRODE SYSTEM REQUIRED AT EACH STRUCTURE |
| | OR MEET EXCEPTION. BASED ON THE PANEL SCHEDULE AND THE |
| | RISER THE NUMBER OF CONDUCTORS IS NOT SHOWN. |
| | PLEASE EXPAND ON THE GROUNDING ELECTRODE ATTACHMENT TO |
| | THE FOUNDATION/FOOTER STEEL. WILL THIS STEEL BE BONDED? |
| | WILL THIS BE USED AS A GROUNDING ELECTRODE? |
| | THE FUTURE BUILDING USE MAY BE OTHER THAN STORAGE. AS |
| | CONDUCTORS ARE NOT SHOWN IT IS NOT CLEAR FOR CODE |
| | COMPLIANCE DETERMINATION. |
| | SEE 250.50,250.122, FOR SIZING AND ATTACHMENT TO FOOTER |
| | STEEL IF NOT MEETING EXCEPTION. |
| | |
| | PLEASE EXPLAIN THE 4INCH FIRE LINES INDICATED AT THE |
| | OUTSIDE OF EACH STRUCTURE. OTHER SHEETS INDICATE THESE |
| | WILL BE CAPPED OFF. |
| | BONDING MAY BE REQUIRED PER 250.104. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |