| 2009-09-25 19:20:22 | |
| | |
| | |
| | ** DENIED PLANS ** |
| | |
| | **SUITE 1450 UNDER 09090526 |
| | ** SUITE 1500 UNDER 09090527 |
| | |
| | ** TWO PERMIT APPLICATIONS SUBMITTED ALTHOUGH ONLY ONE |
| | SET OF PLANS WERE SUBMITTED FOR BOTH FLOORS/SUITES. |
| | |
| | |
| | 1) NOTE: THE SUBMITTED LIGHTING CALCULATIONS FOR ABOVE |
| | SUITE ARE MISSING SOME SPACES/LIGHTING AND SOME |
| | COORDINATION IS NEEDED FOR NUMBER OF FIXTURE, TYPES OF |
| | FIXTURE/WATTAGE OF FIXTURES. |
| | A) PLEASE SEE AREAS 1401,1411, 1400 ARE MISSING. |
| | |
| | B) PLEASE SEE AREA 1412 FOR EXAMPLE WHICH INDICATES |
| | 5-32 WATT FIXTURES AND 2-56W FIXTURES. BASED ON THE |
| | FIXTURE LEGEND THESE ARE NOT CORRECT. |
| | BASED ON THE FIXTURE LEGEND THERE WOULD BE 2-32W, 3-56W |
| | AND 1-14W. IT IS ACTUALLY LESS THAN SHOWN. HOWEVER |
| | RECORD PLANS FOR THE NUMBER AND TYPE OF FIXTURES NEED |
| | TO BE CORRECTED. |
| | |
| | C) PLEASE SPACE 1512 FOR EXAMPLE; CALCULATIONS STATE |
| | 17-32 WATT FIXTURES. HOWEVER BASED ON THE PLANS AND |
| | FIXTURE LEGEND THERE ARE MORE THAN ONE TYPE OF FIXTURE |
| | IN THIS AREA. IN FACT THERE ARE THREE DIFFERENT TYPES |
| | OF FIXTURES. SOME FIXTURES WITH LESS WATTAGE AND SOME |
| | WITH MORE WATTAGE. SPECIFICALLY G FIXTURES WHICH ARE |
| | NOT 32 WATT AS LISTED THEY ARE 50W. ALSO FIXTURE E |
| | WHICH IS NOT 32 IT IS 13W. |
| | |
| | D) PLEASE SEE ROOM 1513 FOR EXAMPLE: CALCULATIONS |
| | INDICATE 23-32W FIXTURES. HOWEVER BASED ON PLANS AND |
| | FIXTURE LEGEND THERE ARE FIXTURES SUCH AS 4-G FIXTURES |
| | WHICH ARE 50WATT FIXTURES. THE COUNT OF THE 32W F/F1 |
| | FIXTURES IS 22. THE ACTUAL WATTAGE IN THIS ROOM IS |
| | HIGHER. PLEASE ADJUST. |
| | |
| | *** KEEP IN MIND TRADE OFFS ARE ONLY PERMITTED WITHIN |
| | THE TENANT SPACE. IT IS NOT PERMITTED TO TRADE COMMON |
| | AREA HALLWAY AREAS WITH LIGHTING WITHIN THE TENANT |
| | SPACE. |
| | 13-415.AB.5, 13-415.B.1. SEE APPENDIX B |
| | |
| | 2) NOTE: PLEASE GO THROUGH PLANS AND COORDINATE ALL |
| | CIRCUITING SO THAT LOADS SHOWN ON THE NUMBER OF |
| | RECEPTACLES CAN BE REVIEWED FOR CODE COMPLIANCE. |
| | |
| | A) EXAMPLE: PLANS SHOW CIRCUIT JBL1-18 IN AREA 1533 AS |
| | A DEDICATED RECEPTACLE HOWEVER PER THE SAME PANEL |
| | SCHEDULE JBL1-18 STATES RECEPTACLES IN ROOM 1520. |
| | ROOM 1520 INDICATES CIRCUIT AS JBL1-29 |
| | |
| | B) EXAMPLE: ROOM 1520 ABOVE NOTES JBL1-29 YET WHEN YOU |
| | REVIEW THIS CIRCUIT ON PANEL SCHEDULE IT STATES ROOM |
| | 1505, 1506. |
| | |
| | C) EXAMPLE: ROOM 1505 AS NOTED ABOVE IS THE WOMEN???S |
| | BATHROOM HOWEVER BASED ON THE PLANS THERE IS NO |
| | ELECTRICAL RECEPTACLES IN THIS AREA. ROOM 1505 IS |
| | COMMON AREA WHY IS THIS BEING FED FROM TENANT |
| | ELECTRICAL PANEL? |
| | ROOM 1506 AS NOTED ON PANEL SCHEDULE IS ACTUALLY THE |
| | WEST STAIRWAY AS SHOWN ON E2.2?? |
| | |
| | D) EXAMPLE: PANEL JBL1 IS A TENANT PANEL. PLEASE |
| | EXPLAIN CIRCUITS 1,3,5,7,9 ETC WHICH ARE ALL SHOWN AS |
| | CIRCUITS IN THE TENANT PANEL YET PER THE PLANS ALL THE |
| | SPACES/ROOM LISTED ARE IN THE COMMON AREAS. |
| | |
| | E) EXAMPLE: PLEASE SEE PANEL L-14 CIRCUIT 11 WHICH IS |
| | LISTED ON THE TENANT PANEL SCHEDULE FEEDING SPACE 1405, |
| | HOWEVER SPACE 1405 ON THE PLANS IS ACTUALLY COMMON AREA |
| | BATHROOM WHICH DOES NOT INDICATE ANY ELECTRICAL. |
| | |
| | F) EXAMPLE: L14-4 ON PLANS WHICH IS LOCATED IN ROOM |
| | 1420 IS ACTUALLY LISTED IN ROOM 1413 ON PANEL SCHEDULE. |
| | |
| | G) EXAMPLE: L14-6 ON PLANS WHICH IS LOCATED IN ROOM |
| | 1420 IS ACTUALLY LISTED IN ROOM 1413 ON PANEL SCHEDULE. |
| | |
| | H) EXAMPLE: L14-8 ON PLANS WHICH IS LOCATED IN ROOM |
| | 1420 IS ACTUALLY LISTED IN ROOM 1413 ON PANEL SCHEDULE. |
| | |
| | I) EXAMPLE: PLEASE SEE PANEL JBL2 CIRCUITS 19 AND 21. |
| | BOTH OF THESE ARE INDICATING RECEPTACLES IN ROOM/AREA |
| | 102, HOWEVER ROOM 1502 DOES NOT SHOW ANY ELECTRICAL |
| | RECEPTACLES AS THIS IS THE VESTIBULE AREA. |
| | |
| | J) EXAMPLE: L14-7 SHOWN ON PLANS IN ROOM 1422 YET PANEL |
| | SCHEDULE INDICATES ROOM 1404 WHICH IS COMMON AREA. |
| | |
| | K) EXAMPLE: L14-9 SHOWN ON PLANS IN ROOM 1422 YET PANEL |
| | SCHEDULE INDICATES ROOM 1404 WHICH IS COMMON AREA. |
| | |
| | L) EXAMPLE: L14-12 SHOWN ON PLANS IN ROOM 1422 YET |
| | PANEL SCHEDULE INDICATES ROOM 1404 WHICH IS COMMON |
| | AREA. |
| | |
| | ETC. |
| | |
| | |
| | ****** IMPORTANT*** |
| | THESE ARE ONLY SOME EXAMPLES OF CIRCUITING FOR 1450 AND |
| | 1500 WHICH DO NOT COORDINATE. PLEASE GO THROUGH ALL |
| | CIRCUITING AS THERE ARE NUMEROUS OTHERS. |
| | LOADS ON CIRCUITS, LOADS ON PANELS AND LOADS ON SERVICE |
| | CAN NOT BE VERIFIED. |
| | SIZING OF OVER CURRENT PROTECTION FOR CIRCUITS ALSO CAN |
| | NOT BE VERIFIED. |
| | |
| | ** TENANT SPACES SHALL BE CIRCUITED FROM THEIR PANELS |
| | AND COMMON AREAS SHOULD BE CIRCUITED FROM HOUSE PANELS. |
| | |
| | 240.4,310.16.220.44,220.42, 240.24A, 240.24B ETC |
| | |
| | 3) NOTE: PLEASE EXPLAIN RISER. RISER INDICATES THE JBH |
| | PANEL FED FROM GUTTER WITH TENANT METER HOWEVER THE |
| | FEED TO TRANSFORMER WHICH FEEDS ALL TENANT PANELS JBL1, |
| | 2 AND 3 YET THERE IS NOT METER ON RISER? |
| | ALSO AS NOTED ABOVE FOR CIRCUITING CIRCUITS SUCH AS |
| | H14-5 STATES CORRIDOR LIGHTING HOWEVER THIS IS |
| | HOUSE/COMMON AREA? THERE ARE ALREADY HOUSE/COMMON AREA |
| | PANELS SHOWN ON RISER. |
| | AS NOTED ABOVE WITH THE CIRCUITING ETC NOT COORDINATED |
| | FOR TENANTS AND COMMON AREAS, REVIEW AND CONFIRMATION |
| | OF LOADS SHOWN ARE UNKNOWN FOR CODE COMPLIANCE. |
| | |
| | NEC 220,215, 210, 240, 310, ETC GIVEN AS GENERAL |
| | CHAPTERS UNTIL PLANS ARE COMPLETE WITH ITEMS ABOVE. |
| | |
| | |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |