| 2009-09-28 16:47:43 | ****PROVISO**** |
| | REVISION REQUIRED BEFORE FIRST INSPECTION |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | SUBMIT A REVISED INSTALLATION SCHEDULE: |
| | |
| | 1. SEE OPENING 5. OPENING SIZE IS 90", SPAN IS 90" WITH |
| | 3.5" EDGE DISTANCE. THE SPAN SHOULD BE A MINIMUM OF 97" |
| | (WITH 90" OPENING AND 3.5" EDGE DISTANCE TOP AND |
| | BOTTOM), AND THIS EXCEEDS THE SPAN PERMITTED ON THE |
| | PRODUCT APPROVAL. PLEASE CLARIFY,SHOW COMPLIANCE, OR |
| | SUBMIT A NEW PRODUCT APPROVAL WHICH MEETS THE DESIGN |
| | REQUIREMENTS OF THIS JOB. FBC R301. SEE OTHER OPENINGS |
| | AND REVISE SPANS AND ANCHOR SPACING AS REQUIRED. |
| | |
| | 2. ACCORDIONS, SPANS ARE SHOWN AS SMALLER THAN THE |
| | OPENING SIZE FOR A WALL MOUNT. SPAN SHOULD BE AT LEAST |
| | 4" LARGER THAN THE OPENING SIZE FOR WALL MOUNT |
| | CONNECTION. SEE OPENING 1, 2, 3, MOST OTHERS. CHECK |
| | ALL; REVISE ALL SPANS AS NECESSARY. REVISE ANCHOR |
| | SPACING IF NEEDED. |
| | |
| | 3. ACCORDIONS, FOR THE FLOOR MOUNT CONNECTIONS, (H, K), |
| | CONCRETE IS RUQIRED TO BE 3KSI MINIMUM PER PAGE 14. |
| | RESIDENTIAL SLABS ARE USUALLY 2500PSI. EITHER PROVIDE |
| | EVIDENCE OF 3000PSI CONCRETE SUBSTRATE OR OTHERWISE |
| | ADDRESS. FEEL FREE TO CONTACT ME TO DISCUSS OPTIONS. |
| | |
| | |