| 2009-10-08 19:42:52 | ** DENIED PLANS ** |
| | |
| | ** SOME OF THE ITEMS BELOW WOULD TYPICALLY BE REDLINED |
| | HOWEVER THERE ARE SEVERAL OF THESE ITEMS WHICH COULD |
| | NOT. |
| | |
| | 1) NOTE: PLANS INDICATE A RECEPTACLE FOR WATER HEATER |
| | CONNECTION. PLEASE SEE 422.30, 422.31 FOR REQUIRED |
| | DISCONNECT AND UNIT TO BE HARD-WIRED. |
| | |
| | 2) NOTE: PLEASE SUBMIT THE FOLLOWING INFORMATION: |
| | A) NO LOAD INFORMATION SHOWN FOR ELECTRICAL PANEL |
| | SCHEDULE. NEC 220. PLEASE ALSO INCLUDE NEW LOADS AND |
| | EXISTING SERVICE LOADS. |
| | B) NO INFORMATION ON WHAT SIZE PANEL IS FEEDING LOADS. |
| | C) NO INFORMATION FOR FEEDERS. 240.4, 310.15B6, 310.16, |
| | 215.5 ETC |
| | D) NO INFORMATION FOR MEANS OF DISCONNECT AT DETACHED |
| | STRUCTURE PER 225.31-225.39 OR 230.70,71. |
| | E) NO INFORMATION ON GROUNDING ELECTRODE SYSTEM AT THE |
| | DETACHED BUILDING PER 250.32, 250.50 |
| | |
| | 3) NOTE: MISSING WALL RECEPTACLE PER 210.52 |
| | |
| | 4) NOTE: MISSING GARAGE RECEPTACLE PER 210.52G ALSO IS |
| | REQUIRED TO BE GFI PER 210.8A2 |
| | |
| | 5) NOTE: *REDLINED SMOKE DETECTOR TO SMOKE ALARM. |
| | NFPA-72 11.5.1, PLEASE ALSO SEE FLORIDA STATUES 553.885 |
| | FOR REQUIRED CARBON MONOXIDE DETECTOR/ALARM. |
| | |
| | 6) NOTE: ARC FAULT PROTECTION PER 210.12 |
| | |
| | 7) NOTE: GFI IN BATHROOM PER 210.8A1. PLAN INDICATES |
| | THE RECEPTACLE BUT NOT THE GFI. |
| | |
| | 8) NOTE: PANEL SCHEDULE INDICATES WALL MOUNTED A/C UNIT |
| | HOWEVER PLANS DO NOT SHOW THE ELECTRICAL RECEPTACLE |
| | LOCATION FOR UNIT. PLANS ONLY INDICATE THE GENERAL |
| | PURPOSE RECEPTACLES. |
| | |
| | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |