2009-09-29 16:31:42 
 ** PROVISO **
  
 ** PLANS TO BE REVISED BEFORE INSPECTION.
  
 1) NOTE: PLEASE SEE 450.3B. ONLY IF MEETING NOTE #3 CAN
 THE MAXIMUM OVER CURRENT PROTECTION BE 500AMPS FOR THE
 TRANSFORMER T1. BASED ON THE CALCULATIONS THIS SHOULD
 BE UNDER 450AMPS. BASED ON 240.6 THE NEXT STANDARD OCP
 IS 450AMPS.
  
 2) NOTE: TIME CLOCK REQUIRED SHALL MEET FBC
 13-415.AB.1.4. SECTION REQUIRES AN ASTRONOMICAL TYPE
 TIME CLOCK WITH BACK UP FOR PROGRAMMING MEETING MINIMUM
 OF 10HRS UNDER SECTION GIVEN FOR PROGRAMMING.
  
 3) NOTE: SIGNED, DATED AND SEALED WIND LOAD
 CALCULATIONS REQUIRED TO BE SUBMITTED FOR BLDG REVIEW.
  
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  