2010-01-14 10:28:30BUILDING PLAN REVIEW
 PERMIT: 09090440
 ADD: 836 BELVEDERE RD
 CONT: CORPORATE PROPERTY SERVICES, INC.
 TEL: (954)426-5144
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING REVIEW-BUILDING APPROVED WITH EXCEPTION!
  
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 1) THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE
 TO CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR
 TO INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND
 THE ASSESSMENT OF RE-INSPECTION FEE(S).
 CONTRACTORS OPTION: TO SUBMIT PRODUCT APPROVALS A THIS
 TIME OR BEFORE INSULATION OF PRODUCT BEFORE THE FRAMING
 INSPECTION, LIST OF PRODUCT APPROVALS REQUIRED BY RULE
 9B-72:
 A) WINDOWS- STOREFRONT AND OPERABLE
 B) MULLIONS HORIZONTAL OR VERTICAL
 C) EXTERIOR DOORS GLAZED
 D) EXTERIOR DOORS METAL
 E) WALL LOUVERS
 F) EFIS WALL SYSTEMS
 G) ROOFING ASSEMBLIES
 H) PRE-ENGINEERED A/C STANDS
 I) STORM PANELS OR SHUTTERS IF WINDOWS ARE NOT TESTED
 TO LARGE MISSILE IMPACT RESISTANCE
  
 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 2) SHEET A4.0 & A4.1 THE WINDOW AND DOOR PRESSURES ALSO
 APPEAR TO BE LOW IN POSITIVE AND NEGATIVE FOR ZONE 4,
 INTERIOR ZONES AND FOR ZONE 5 END ZONES. PLEASE REVIEW
 1609.1.1 IT REFERENCES ASCE 7-05 FOR PRESSURES AND END
 ZONE LOCATIONS.
  
 8)WIND REPORT AND RATIONAL ANALYSIS REQUIRES TWO
 ORIGINAL SIGNED & SEALED SETS BE SUBMITTED FOR BUILDING
 PLAN REVIEW TO DEMONSTRATE COMPLIANCE WITH FBC-M
 301.12.. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS
 ROOF TOP MECHANICAL EQUIPMENT: 301.13 FBC MECHANICAL.
 WIND RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST WIND PRESSURES ON THE EQUIPMENT AND
 THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, BUILDING. NOTE THIS DOES NOT
 ONLY MEAN THE ATTACHMENT OF THE UNIT TO THE BASE
 SUPPORT BUT THE EXTERIOR CABINET OF THE UNIT ITSELF.
 ENGINEERING LETTERS WILL SUFFICE.
  
 3) BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
 PLEASE NOTE THE ROOFING PERMIT WILL BE A SEPARATE
 PERMIT AND WILL NEED TO INCLUDE THE PRODUCT APPROVAL,
 INDICATE WHICH SUB-SYSTEM TO BE INSTALLED ON THIS
 PROJECT. IF A MIAMI-DADE NOA IS SUBMITTED IT MAY HAVE
 VARIOUS OPTIONS FOR FASTENING OF THE ROOFING PRODUCT
 AND INSULATION WITHIN EACH SUB-SYSTEM.
 EACH OPTION WILL HAVE IT OWN DESIGN PRESSURES. THE
 PRODUCT APPROVAL WILL ALSO STATE IF EACH SYSTEM CAN
 HAVE ENHANCED FASTENING (LIMITATION 7) OR LIMITATION 9
 WHICH DOES NOT ALLOW FOR ENHANCED FASTENING.
  
 4) 2ND REQUEST, BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
 THE ISSUE YOU WILL NEED TO ADDRESS IS ROOF INSULATION,
 A MINIMUM R-VALUE OF R-29.5 NEW R-VALUE, NEW ENERGY
 CALCS WILL NEED TO BE OBTAINED ( ENERGY CALCULATION) .
 UNDER THE ROOFING PERMIT PLEASE PROVIDE A ROOF
 INSULATION PLAN.
  
 5) SHEET S3.0 ROOF PLAN ONLY INDICATES PRESSURES FOR
 THE INTERIOR ZONES (ZONE 1) AND CORNER ZONES (ZONE 2)
 BUT NO ZONE 3 PRESSURES FOR THE CORNER ZONES.
 ITS TRUE THE BACK OF THE BUILDING DOES HAVE A 4'-0''
 PARAPET ELIMINATING THESE ZONES BUT THE
 FRONT OF THE BUILDING DOES NOT HAVE A 3'-0'' PARAPET
 WHICH WOULD ELIMINATE ZONE 3 PRESSURES WILL BE AS HIGH
 AS -89 FOR AN "B" EXPOSURE.
  
 6) SHEET A5.1 DETAIL F & A5.2 DETAIL J & I ARE ALL WALL
 SECTION AT THE TOWER , IN ALL CASES THERE IS AN
 EXPANSION JOINT/ COLD JOINT WHICH ALLOWS WATER TO SEEP
 INTO THE FRAMED WALL, ALLOWING THE WOOD TO ROT. THE
 OTHER ISSUE AS STATED EARLIER THE REQUIREMENT UNDER
 2603.8.1 TO ALLOW FOR A VISUAL INSPECTION FOR TERMITES,
 WE NORMALLY SEE THIS AREA POURED IN CONCRETE 8 INCHES
 HIGHER THAN THE SLAB SO THERE IS NO COLD JOINT AND THE
 STUCCO FINISH IS APPLIED DIRECTLY TO THE CONCRETE AS IF
 A MASONRY WALL. PLANS STILL INDICATE 8??? BLOCK WITH
 THE NEW POURED WALL SECTION, THERE IS STILL A VERTICAL
 COLD JOINT. THE OTHER ISSUE IS STEM WALL STARTS WITH A
 12 INCH WIDE BLOCK THEN STEPS BACK TO 8 INCH WHICH ALSO
 ALLOWS THE TERMITES TO CREATE TUNNELS UP THE BLOCK WORK
 AND GAIN ENTRY INTO THE BUILDING.
 2304.11.2.4 SLEEPERS AND SILLS. SLEEPERS AND SILLS ON A
 CONCRETE OR MASONRY SLAB THAT IS IN DIRECT CONTACT WITH
 EARTH SHALL BE OF NATURALLY DURABLE OR
 PRESERVATIVE-TREATED WOOD.
  
 2304.11.2.6 WOOD SIDING. CLEARANCE BETWEEN WOOD SIDING
 AND EARTH ON THE EXTERIOR OF A BUILDING SHALL NOT BE
 LESS THAN 6 INCHES (152 MM) EXCEPT WHERE SIDING,
 SHEATHING AND WALL FRAMING ARE OF NATURALLY DURABLE OR
 PRESERVATIVE-TREATED WOOD.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  