| 2010-01-14 10:28:30 | BUILDING PLAN REVIEW |
| | PERMIT: 09090440 |
| | ADD: 836 BELVEDERE RD |
| | CONT: CORPORATE PROPERTY SERVICES, INC. |
| | TEL: (954)426-5144 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | BUILDING REVIEW-BUILDING APPROVED WITH EXCEPTION! |
| | |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). |
| | |
| | 1) THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE |
| | TO CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR |
| | TO INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND |
| | THE ASSESSMENT OF RE-INSPECTION FEE(S). |
| | CONTRACTORS OPTION: TO SUBMIT PRODUCT APPROVALS A THIS |
| | TIME OR BEFORE INSULATION OF PRODUCT BEFORE THE FRAMING |
| | INSPECTION, LIST OF PRODUCT APPROVALS REQUIRED BY RULE |
| | 9B-72: |
| | A) WINDOWS- STOREFRONT AND OPERABLE |
| | B) MULLIONS HORIZONTAL OR VERTICAL |
| | C) EXTERIOR DOORS GLAZED |
| | D) EXTERIOR DOORS METAL |
| | E) WALL LOUVERS |
| | F) EFIS WALL SYSTEMS |
| | G) ROOFING ASSEMBLIES |
| | H) PRE-ENGINEERED A/C STANDS |
| | I) STORM PANELS OR SHUTTERS IF WINDOWS ARE NOT TESTED |
| | TO LARGE MISSILE IMPACT RESISTANCE |
| | |
| | 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 2) SHEET A4.0 & A4.1 THE WINDOW AND DOOR PRESSURES ALSO |
| | APPEAR TO BE LOW IN POSITIVE AND NEGATIVE FOR ZONE 4, |
| | INTERIOR ZONES AND FOR ZONE 5 END ZONES. PLEASE REVIEW |
| | 1609.1.1 IT REFERENCES ASCE 7-05 FOR PRESSURES AND END |
| | ZONE LOCATIONS. |
| | |
| | 8)WIND REPORT AND RATIONAL ANALYSIS REQUIRES TWO |
| | ORIGINAL SIGNED & SEALED SETS BE SUBMITTED FOR BUILDING |
| | PLAN REVIEW TO DEMONSTRATE COMPLIANCE WITH FBC-M |
| | 301.12.. PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING |
| | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| | DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | ROOF TOP MECHANICAL EQUIPMENT: 301.13 FBC MECHANICAL. |
| | WIND RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND |
| | SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND |
| | INSTALLED TO RESIST WIND PRESSURES ON THE EQUIPMENT AND |
| | THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE |
| | FLORIDA BUILDING CODE, BUILDING. NOTE THIS DOES NOT |
| | ONLY MEAN THE ATTACHMENT OF THE UNIT TO THE BASE |
| | SUPPORT BUT THE EXTERIOR CABINET OF THE UNIT ITSELF. |
| | ENGINEERING LETTERS WILL SUFFICE. |
| | |
| | 3) BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). |
| | PLEASE NOTE THE ROOFING PERMIT WILL BE A SEPARATE |
| | PERMIT AND WILL NEED TO INCLUDE THE PRODUCT APPROVAL, |
| | INDICATE WHICH SUB-SYSTEM TO BE INSTALLED ON THIS |
| | PROJECT. IF A MIAMI-DADE NOA IS SUBMITTED IT MAY HAVE |
| | VARIOUS OPTIONS FOR FASTENING OF THE ROOFING PRODUCT |
| | AND INSULATION WITHIN EACH SUB-SYSTEM. |
| | EACH OPTION WILL HAVE IT OWN DESIGN PRESSURES. THE |
| | PRODUCT APPROVAL WILL ALSO STATE IF EACH SYSTEM CAN |
| | HAVE ENHANCED FASTENING (LIMITATION 7) OR LIMITATION 9 |
| | WHICH DOES NOT ALLOW FOR ENHANCED FASTENING. |
| | |
| | 4) 2ND REQUEST, BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). |
| | THE ISSUE YOU WILL NEED TO ADDRESS IS ROOF INSULATION, |
| | A MINIMUM R-VALUE OF R-29.5 NEW R-VALUE, NEW ENERGY |
| | CALCS WILL NEED TO BE OBTAINED ( ENERGY CALCULATION) . |
| | UNDER THE ROOFING PERMIT PLEASE PROVIDE A ROOF |
| | INSULATION PLAN. |
| | |
| | 5) SHEET S3.0 ROOF PLAN ONLY INDICATES PRESSURES FOR |
| | THE INTERIOR ZONES (ZONE 1) AND CORNER ZONES (ZONE 2) |
| | BUT NO ZONE 3 PRESSURES FOR THE CORNER ZONES. |
| | ITS TRUE THE BACK OF THE BUILDING DOES HAVE A 4'-0'' |
| | PARAPET ELIMINATING THESE ZONES BUT THE |
| | FRONT OF THE BUILDING DOES NOT HAVE A 3'-0'' PARAPET |
| | WHICH WOULD ELIMINATE ZONE 3 PRESSURES WILL BE AS HIGH |
| | AS -89 FOR AN "B" EXPOSURE. |
| | |
| | 6) SHEET A5.1 DETAIL F & A5.2 DETAIL J & I ARE ALL WALL |
| | SECTION AT THE TOWER , IN ALL CASES THERE IS AN |
| | EXPANSION JOINT/ COLD JOINT WHICH ALLOWS WATER TO SEEP |
| | INTO THE FRAMED WALL, ALLOWING THE WOOD TO ROT. THE |
| | OTHER ISSUE AS STATED EARLIER THE REQUIREMENT UNDER |
| | 2603.8.1 TO ALLOW FOR A VISUAL INSPECTION FOR TERMITES, |
| | WE NORMALLY SEE THIS AREA POURED IN CONCRETE 8 INCHES |
| | HIGHER THAN THE SLAB SO THERE IS NO COLD JOINT AND THE |
| | STUCCO FINISH IS APPLIED DIRECTLY TO THE CONCRETE AS IF |
| | A MASONRY WALL. PLANS STILL INDICATE 8??? BLOCK WITH |
| | THE NEW POURED WALL SECTION, THERE IS STILL A VERTICAL |
| | COLD JOINT. THE OTHER ISSUE IS STEM WALL STARTS WITH A |
| | 12 INCH WIDE BLOCK THEN STEPS BACK TO 8 INCH WHICH ALSO |
| | ALLOWS THE TERMITES TO CREATE TUNNELS UP THE BLOCK WORK |
| | AND GAIN ENTRY INTO THE BUILDING. |
| | 2304.11.2.4 SLEEPERS AND SILLS. SLEEPERS AND SILLS ON A |
| | CONCRETE OR MASONRY SLAB THAT IS IN DIRECT CONTACT WITH |
| | EARTH SHALL BE OF NATURALLY DURABLE OR |
| | PRESERVATIVE-TREATED WOOD. |
| | |
| | 2304.11.2.6 WOOD SIDING. CLEARANCE BETWEEN WOOD SIDING |
| | AND EARTH ON THE EXTERIOR OF A BUILDING SHALL NOT BE |
| | LESS THAN 6 INCHES (152 MM) EXCEPT WHERE SIDING, |
| | SHEATHING AND WALL FRAMING ARE OF NATURALLY DURABLE OR |
| | PRESERVATIVE-TREATED WOOD. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |