Plan Review Notes
Plan Review Notes For Permit 09090440
Permit Number 09090440
Review Stop G
Sequence Number 2
Notes
Date Text
2009-12-16 08:01:12PASSED/PROVISO
  
 REVISION REQUIRED.
  
 A. A SHUT OFF VALVE AND UNION ARE REQUIRED UPSTREAM OF
 THE EMERGENCY SHUT OFF VAVLE FOR THE HOOD.
 B. PIPE SIZE FOR THE DROP TO W/H-1, (1" REQD), AND THE
 PIPE PREVIOUS TO SAID DROP, (1-1/4" REQD), TO BE
 CORRECTED.
 C. DELIVERY PRESSURE TO BE INDICATED AS 1/2 PSI NOT 7"
 WC. TABLE 402.4(2).