| 2009-12-16 08:01:12 | PASSED/PROVISO | | | | | | REVISION REQUIRED. | | | | | | A. A SHUT OFF VALVE AND UNION ARE REQUIRED UPSTREAM OF | | | THE EMERGENCY SHUT OFF VAVLE FOR THE HOOD. | | | B. PIPE SIZE FOR THE DROP TO W/H-1, (1" REQD), AND THE | | | PIPE PREVIOUS TO SAID DROP, (1-1/4" REQD), TO BE | | | CORRECTED. | | | C. DELIVERY PRESSURE TO BE INDICATED AS 1/2 PSI NOT 7" | | | WC. TABLE 402.4(2). |
|