| Date |
Text |
| 2009-10-08 17:47:40 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 FUEL GAS |
| | FBC-2007 CHAPTER 1 |
| | WEST PALM BEACH CITY CODE OF ORDINANCES |
| | |
| | 1. SHT A3.0 NOTE INDICATING THE CONDENSATE FROM THE |
| | HVAC UNITS ON THE ROOF TO DRAIN TO THE MOP SINK. THIS |
| | IS PROHIBITED PER ARTICLE III SECTION 90-125(5). |
| | CONDENSATE SHALL BE PIPED SEPARATELY OUT OF THE |
| | BUILDING AND DRAINED INTO A DRYWELL, TO A PLANTED AREA |
| | OR CONNECT TO A CATCH BASIN. |
| | |
| | 2. SHTS A3.0 & A6.4.0 DETAIL 4. PLEASE INDICATE THE |
| | SIZE OF THE DOWNSPOUTS. TABLE 1106.2. |
| | |
| | 3. THE GREASE INTERCEPTOR SIZE SHALL BE DETERMINED BY |
| | THE UTILITY DEPT., INDUSTRIAL PRETREATMENT, |
| | ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT HOLLY MCGRATH, |
| | LABORATORY SUPERVISOR BY PHONE (561) 822-2271, BY FAX |
| | (561) 822-2279 OR E-MAIL [email protected]. A WRITTEN |
| | DETERMINATION IS REQUIRED. |
| | |
| | 4. SHT P2.0 KEY NOTES #11 CONDENSATE NOT APPROVED IN |
| | THE SANITARY SYSTEM. ARTICLE III SECTION 90-125(5). SEE |
| | COMMENT #1. |
| | |
| | 5. SHT P3.0 FLOOR PLAN SHOWS A KEY NOTE #25 INDICATOR, |
| | BUT NO KEY NOTE #25 SHOWN. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 6. SHT P3.0 COLD WATER SUBBPL SHOWN TO KEY NOT 21 ON |
| | THE FLOOR PLAN IS NOT CONNECTED TO THE COLD WATER MAIN. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 7. SHT P5.0 SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING |
| | INFORMATION IS REQUIRED FOR THE PERMIT. |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR |
| | 2007 FUEL GAS CODE. - LENGTHS NOT INDICATED. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2007 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED WHEN |
| | COMMENT "7-A" IS ADDRESSED. |
| | |
| | E. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2007 FUEL |
| | GAS CODE SECTION 304 & RESIDENTIAL CODE SECTION G2407. |
| | |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - FPU PROVIDES 1/2 |
| | PSI (12"-14" WC) OR 2 PSI. NOT 1/4 PSI (7" WC). SEE |
| | TABLE 402.4(2). |
| | |
| | G. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2007 FUEL GAS CODE |
| | SECS. 502 THRU 505 & RESIDENTIAL CODE SECS. G2426 THRU |
| | G2429. |
| | |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE |
| | SEC. G2413.2. |
| | |
| | I. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | J. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | K. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. - NO MANUAL SHUT OFF VALVE |
| | OR UNION SHOWN. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |