Plan Review Notes
Plan Review Notes For Permit 09090440
Permit Number 09090440
Review Stop P
Sequence Number 1
Notes
Date Text
2009-10-08 17:47:40DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 FUEL GAS
 FBC-2007 CHAPTER 1
 WEST PALM BEACH CITY CODE OF ORDINANCES
  
 1. SHT A3.0 NOTE INDICATING THE CONDENSATE FROM THE
 HVAC UNITS ON THE ROOF TO DRAIN TO THE MOP SINK. THIS
 IS PROHIBITED PER ARTICLE III SECTION 90-125(5).
 CONDENSATE SHALL BE PIPED SEPARATELY OUT OF THE
 BUILDING AND DRAINED INTO A DRYWELL, TO A PLANTED AREA
 OR CONNECT TO A CATCH BASIN.
  
 2. SHTS A3.0 & A6.4.0 DETAIL 4. PLEASE INDICATE THE
 SIZE OF THE DOWNSPOUTS. TABLE 1106.2.
  
 3. THE GREASE INTERCEPTOR SIZE SHALL BE DETERMINED BY
 THE UTILITY DEPT., INDUSTRIAL PRETREATMENT,
 ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT HOLLY MCGRATH,
 LABORATORY SUPERVISOR BY PHONE (561) 822-2271, BY FAX
 (561) 822-2279 OR E-MAIL [email protected]. A WRITTEN
 DETERMINATION IS REQUIRED.
  
 4. SHT P2.0 KEY NOTES #11 CONDENSATE NOT APPROVED IN
 THE SANITARY SYSTEM. ARTICLE III SECTION 90-125(5). SEE
 COMMENT #1.
  
 5. SHT P3.0 FLOOR PLAN SHOWS A KEY NOTE #25 INDICATOR,
 BUT NO KEY NOTE #25 SHOWN. PLEASE CLARIFY. SECTION
 106.1.1.
  
 6. SHT P3.0 COLD WATER SUBBPL SHOWN TO KEY NOT 21 ON
 THE FLOOR PLAN IS NOT CONNECTED TO THE COLD WATER MAIN.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 7. SHT P5.0 SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE PERMIT.
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE. - LENGTHS NOT INDICATED.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED WHEN
 COMMENT "7-A" IS ADDRESSED.
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2007 FUEL
 GAS CODE SECTION 304 & RESIDENTIAL CODE SECTION G2407.
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - FPU PROVIDES 1/2
 PSI (12"-14" WC) OR 2 PSI. NOT 1/4 PSI (7" WC). SEE
 TABLE 402.4(2).
  
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2007 FUEL GAS CODE
 SECS. 502 THRU 505 & RESIDENTIAL CODE SECS. G2426 THRU
 G2429.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE
 SEC. G2413.2.
  
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 K. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. - NO MANUAL SHUT OFF VALVE
 OR UNION SHOWN.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved